The boiler is internally protected for water
temperature using the LMU64 temperature sensors.
Also the D.H.W. cylinder is protected via the signal
received from the cylinder sensor. Both boiler and
hot water cylinder frost protection settings are pre
-
programmed in the boiler controls, not the QAA73
programmable room unit.
Primary circuit pump
The primary circuit pump is designated Q8. This
must be connected to the boiler at terminals
‘
X2
-
03,
Q8 primary circuit pump contactor
’.
The control
signal is a start stop control that must be wired via
suitable contactors and hand/auto switches for
maintenance purposes.
Flow rate and resistance for the primary pump must
be sized in accordance with the flow requirements
for the boiler and the resistance requirements of
both the boiler and the primary circuit.
Note: The control does not incorporate a facility for
switching duty/standby pumps. If required this must
be facilitated externally to these controls.
Heating circuit pump
The heating pump is designated Q1. This must be
connected to the boiler at terminals
‘
X2
-
02, Q1
heating circuit pump contactor
’.
The control signal is
a start stop control that must be wired via suitable
contactors and hand/auto switches for maintenance
purposes.
Flow rate and resistance for the heating pump must
be sized in accordance with the flow requirements
for the heating circuit and the resistance
requirements of the heating circuit.
Note:
The control does not incorporate a facility for
switching duty/standby pumps. If required this must
be facilitated externally to these controls.
Second heating circuit pump
The second heating circuit pump is designated Q2.
This must be connected to the boiler using the clip
-
in relay terminals
‘
X52
-
02, Q2 2nd circuit pump
contactor
’.
Flow rate and resistance for the second heating
circuit pump must be sized in accordance with the
flow requirements for the second heating circuit and
the resistance requirements of the second heating
circuit.
Note:
The control does not incorporate a facility for
switching duty/standby pumps. If required this must
be facilitated externally to these controls.
D.H.W. Circuit pump
The D.H.W. circuit pump is designated Q3. This
must be connected to the boiler at terminals
‘
X2
-
04,
Q3 DHW cylinder pump contactor
’.
The control
signal is a start stop control that must be wired via
suitable contactors and hand/auto switches for
maintenance purposes.
Flow rate and resistance for the D.H.W. circuit pump
must be sized in accordance with the flow
requirements for the cylinder and the resistance
requirements of the cylinder and pipework circuit.
Note:
The control does not incorporate a facility for
switching duty/standby pumps. If required this must
be facilitated externally to these controls.
Room programmer
The single room programmer, QAA73, must be
installed in the location most suitable for providing
accurate space heating comfort control with the first
heating circuit area (circuit using pump Q1). This
must be connected to the boiler at terminals
‘
X10
-
01, room unit QAA73
’.
Wiring should be completed using a 1.5mm² twisted
pair shielded cable run separately to any mains
cables to prevent electrical interference.
External air sensor
This must be installed on a North facing wall to
prevent solar heating of the sensor and away from
heat emitting items such as ventilation outlets.
Connection is directly to the boiler at terminals
‘
X10
-
06, external air sensor QAC34
’.
Wiring should be
completed using a 1.5mm² twisted pair shielded
cable, run separately to any mains cables to prevent
electrical interference. For further details regarding
the sensor specification and fitting requirements
refer to appendix A at the rear of this manaul.
D.H.W. Cylinder sensor
This should be fitted to the cylinder using the pocket
provided on the cylinder to ensure accurate
temperature detection. Connection is directly to the
boiler at terminals
’
X10
-
05, D.H.W. cylinder sensor
QAL36
’.
Wiring should be completed using a
1.5mm² twisted pair shielded cable, run separately
to any mains cables to prevent electrical
interference.
Note:
The cable supplied with the sensor may
require extending.
Содержание QAA73.210
Страница 2: ......
Страница 5: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B iii...
Страница 6: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B iv...
Страница 15: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 9 4 0 Operation 7 2 4 1 5 3 6...
Страница 17: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 11...
Страница 18: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 12...
Страница 19: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 13...
Страница 20: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 4 2 Programming BMU Parameters 14...
Страница 34: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 26...
Страница 37: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 29...
Страница 41: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 33...
Страница 43: ......