HAMWORTHY HEATING LTD

 

 

QAA73.210 

 

Programmable Room Unit

 

 

500001305/B

 

 

12

 

5.0 Operational fault finding

 

 

 

No display on the room unit:

 

 

• 

Is the heating plant's main switch turned on?

 

• 

Are the fuses in order?

 

• 

Check the wiring

 

 

Room  unit  displays  a  wrong  time  of  day  or  a 

wrong date:

 

 

• 

Set the right time of day, the right date and the 
year  on  the  room  unit  if  the  QAA73.210  is  the 
clock master 

 

• 

Set the correct time of day and the date on the 
clock master (if present)

 

 

Boiler control does not switch on

 

 

• 

Does boiler control really have to operate?

 

• 

Press boiler control

s lock

-

out reset button

 

• 

Check  the  control  thermostat  (TR)  and  the 
manual reset safety limit thermostat (STB)

 

• 

Check wiring and fuse of boiler control

 

• 

Check the communication link to boiler control

 

 

The  room  temperature  does  not  agree  with  the 

required temperature level:

 

 

• 

Does the room temperature setpoint agree with 
the required temperature level? 

 

• 

Is the required operating mode indicated?

 

• 

Are  weekday,  time  of  day  and  the  displayed 
heating 

program 

correct?

 

(Info displays)

 

• 

Has the heating curve slope been correctly set? 

 

• 

Check wiring of outside sensor

 

• 

Has  the 

Nominal  room  temperature  setpoint

” 

with  the 

Parallel  displacement  of  the  heating 

curve

” 

been  calibrated  based  on  the  effective 

room temperature?

 

• 

Check boiler control

 

 

D.h.w. is not being heated:

 

 

• 

Has the button for d.h.w. heating been pressed?

 

• 

Check setpoint of the d.h.w. temperature

 

• 

Check d.h.w. function of boiler control

 

6.0 Technical Data

 

 

OpenTherm Interface:

 

 

Terminals

   

 

2

-

wire (interchangeable

 

Cable length

  

 

max. 50m

 

Cable resistance

   

max. 2 x 5

Ω

 

Power consumption

 

20mW (typically)

 

 

Safety class

  

 

III to EN 60 730

 

 

 

 

 

when mounted in 

   

 

 

 

 

compliance with 

   

 

 

 

 

regulations

 

 

Degree of Protection

 

IP 20 to EN 60529

 

 

Contamination

 

 

Environment to EN 60730

 

 

Operation

   

 

EN 60721

-

3

-

3 Class 3K 5

 

• 

Temperatures

 

0....50°C

 

• 

Humidity

 

 

< 85 % r.h.

 

 

Transport

   

 

EN 60721

-

3

-

2 Class 2K 3

 

• 

Temperatures

 

-

25... 70°C

 

• 

Humidity

 

 

< 95 % r.h.

 

 

Storage

 

 

 

EN 60721

-

3

-

1 Class 1K 3

 

• 

Temperatures

 

-

20... 70°C

 

• 

Humidity

 

 

< 95 % r.h.

 

 

CE Conformity

 

 

EMC directive

 

 

2004/108/EC

 

-

Immunity

   

 

EN 60730

-

1

 

-

Emmissions

 

 

EN 60730

-

1

 

Reduction of 

 

Hazardous substances

 

2002/95/EC

 

 

Measuring Range

   

0... 50°C

 

According to EN12098:

 

Range 15...25°C

   

within tol. Of 1.3K

 

Range 0...15°C 

 

or 25...50°C

  

 

within tol. Of 1.6K

 

Resolution

   

 

1/10K

 

 

Back

-

up of Time Switch

 

min. 12h

 

Software Class

 

 

A to EN 60 730

 

Weight

 

 

 

approx 0.115kg

 

 

 

 

Содержание QAA73.210

Страница 1: ...Room Unit For Single Boiler Installations INSTALLATION COMMISSIONING AND SERVICING INSTRUCTIONS IMPORTANT NOTE THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING COMMISSIONING OPERATING...

Страница 2: ......

Страница 3: ...210 PROGRAMMABLE ROOM UNIT For Single Boiler Applications Installation Commissioning and Operating Instructions i NOTE THESE INSTRUCTIONS SHOULD BE READ AND UNDERSTOOD BEFORE ATTEMPTING TO INSTALL CO...

Страница 4: ...sioning 5 4 0 Operation 10 4 1 Display 4 2 Programming BMU parameters 4 3 Room unit settings 4 4Time switch program 4 5 Cooling circuit 4 6 Domestic Hot Water 4 7 Configuration 4 8 Functions 5 0 Fault...

Страница 5: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B iii...

Страница 6: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B iv...

Страница 7: ...dual basis D h w program with up to 4 heating periods per day can be selected on an individual basis Holiday program The heating programs and the d h w program can be reset to their default settings P...

Страница 8: ...erature as accurately as possible without being affected by direct solar radiation or other heating or cooling sources Mounting height should be approximately 1 5 meters above the floor The unit can b...

Страница 9: ...t the bottom and remove the base from the housing front Pull the interface cable through the opening of the base and connect it to the screw terminals Fit the base to the walls with screws Engage the...

Страница 10: ...or the OpenTherm communication interface and the QAA73 room controller is supplied from the boiler LMU64 controller Cables used for installing the OpenTherm communication interface power supply must h...

Страница 11: ...cations and details regarding which parameters to change please refer to the relevant section of this manual Buttons Explanation 1 Press the Info button for at least 3 seconds This will take you direc...

Страница 12: ...ttons to select the required user level To confirm press OK You are now on the required user level User levels The user levels only allow authorized user groups to make settings To reach the required...

Страница 13: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 7 Overview of user Parameters Continued on next page...

Страница 14: ...Room Unit 500001305 B 8 Continued from previous page The above table shows all available settings up to the heating engineer level However certain operating lines may be hidden depending on the type...

Страница 15: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 9 4 0 Operation 7 2 4 1 5 3 6...

Страница 16: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 10 4 1 Display Please see the previous table for the descriptions of the individual display icons...

Страница 17: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 11...

Страница 18: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 12...

Страница 19: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 13...

Страница 20: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 4 2 Programming BMU Parameters 14...

Страница 21: ...apply This setting must be made before the switching times are entered For every day on which other switching times shall apply the pre selection of the individual day with subsequent entry of the swi...

Страница 22: ...re setpoint is active the rooms will be heated according to the adjustment made with the setpoint buttons The adjustment made with the buttons is only active in automatic and continuous operation The...

Страница 23: ...es the flow temperature setpoint based on the selected heating curve The result is a constant room temperature irrespective of outside temperature variations By changing the setting the slope of the h...

Страница 24: ...the summer winter changeover temperature a fixed switching differ ential is compared with the attenuated outside temperature Note This func tion only acts in automatic mode The 24 hour heating limit...

Страница 25: ...C KORR Constant for room influence TRx Actual value of the room temperature TRw Room temperature setpoint TRwk Room temperature setpoint readjusted As the example shows if the room temperature is 2 C...

Страница 26: ...must be enabled to act on the relevant heating circuits There may be no thermostatic radiator valves in the reference room If such valves are present they must be set to their fully open position Qui...

Страница 27: ...ential will become greater The pumps are switched on and off less often The room temperature varies within a wider band With pump heating circuits the amount of heat supplied is controlled by switchin...

Страница 28: ...ature setpoint COMFR During nominal operation the nominal d h w setpoint is maintained It is possible to use 2 different d h w temperature setpoints The temperature setpoint during normal d h w operat...

Страница 29: ...e next day when d h w is heated for the first time This function is possible only when d h w heating is released by the d h w heating program Dwelling time at legionella function setpoint L TIME The s...

Страница 30: ...om influence AMBON must be activated for the required heating circuits and in addition an outside sensor must be connected Room influence The room influence acts on the room temperature setpoint The d...

Страница 31: ...QAA73 210 Programmable Room Unit 500001305 B 4 8 4 Fix flow temperature setpoint The setpoint has to be set manually Note The room influence AMBON must be set to OFF and in addition no outside sensor...

Страница 32: ...e been correctly set Check wiring of outside sensor Has the Nominal room temperature setpoint with the Parallel displacement of the heating curve been calibrated based on the effective room temperatur...

Страница 33: ...porate a facility for switching duty standby pumps If required this must be facilitated externally to these controls Room programmer The single room programmer QAA73 must be installed in the location...

Страница 34: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 26...

Страница 35: ...not incorporate a facility for switching duty standby pumps If required this must be facilitated externally to these controls Heating circuit pump The heating pump is designated Q1 This must be connec...

Страница 36: ...o any mains cables to prevent electrical interference Note The cable supplied with the sensor may require extending Features available with this system 7 Day time clock with 4 periods each day for hea...

Страница 37: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 29...

Страница 38: ...for boiler LMU wiring connection zone water temperature sensor QAL36 and immersion pocket part number 563605339 Fitting second heating circuit clip in relay kit AGU2 500A109 The clip in relay is requ...

Страница 39: ...e requirements of the second heating circuit Note The control does not incorporate a facility for switching duty standby pumps If required this must be facilitated externally to these controls D H W C...

Страница 40: ...ter circuit Auto summer winter time change BST to GMT Holiday program Frost protection for building Frost protection for boiler Frost protection for hot water cylinder Reduced temperature night setbac...

Страница 41: ...HAMWORTHY HEATING LTD QAA73 210 Programmable Room Unit 500001305 B 33...

Страница 42: ...to illustration below For wall mounting a cable entry gland Pg 11 can be fitted to the bottom of the housing External Sensor QAC34 Type Ref Sensing Element Range C Tolerance K Time Constant min Weight...

Страница 43: ......

Страница 44: ...blin 12 Ireland tel 00 353 141 91919 fax 00 353 145 84806 email info hevac ie Scotland Sales Service McDowall Modular Services 2 Penson Road Queenslie Industrial Estate Glasgow G33 4AG tel 0141 336 87...

Отзывы: