HAMWORTHY HEATING LTD. PUREWELL AUTOMATIC IGNITION 500001035/G
29
Figure No. 16 - Diagram of ‘Hi’ Flow Gas Valve Assembly (Natural Gas Only)
PUREWELL 95, 100 (L/L), 105 & 120kW Automatic
& WARMWELL HE 140 Automatic.
The ‘Flowshare’ gas valve assembly is designed to
pass the correct quantity of gas at the nominal inlet
pressure of 20mbar and a maximum inlet pressure of
25mbar.
Refer to Figure No. 1 to find low fire/start and high fire
gas pressures for the boiler being fired.
Fit a manometer (suitable for 30mbar) onto gas
manifold pressure tapping point.
Light the boiler. Remove protective cap from the Hi/
Lo pressure regulator.
Turn the Hi/Lo valve high fire pressure regulator (outer
nut) clockwise until the pressure stops increasing.
Loosen Throttle locking nut (if fitted) and rotate the
throttle valve adjuster screw until the manifold
pressure is a approx. 0.5mbar greater than the
required high fire gas pressure.
Tighten the locking nut (if fitted) on the throttle adjuster
screw.
Turn the Hi/Lo valve high fire rate adjuster anti-
clockwise to fine trim the high fire pressure.
Refer to Figure No. 15 for procedure on how to adjust
valves for correct low fire/start gas pressures.
NOTE! Honeywell valves shown in diagram.
Содержание Purewell
Страница 4: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G ii THIS PAGE LEFT INTENTIONALLY BLANK ...
Страница 19: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G 13 Figure No 7a Exploded View of Casing Set ...
Страница 28: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G 22 Figure No 10 General Layout Front View ...
Страница 40: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G 34 THIS PAGE LEFT INTENTIONALLY BLANK ...