HAMWORTHY HEATING LTD. PUREWELL AUTOMATIC IGNITION 500001035/G
28
Figure No 15 - Diagram of Automatic Gas Valves.
ADJUSTMENT PROCEDURE.
Refer to Figure No. 1 to find the low fire/start and high
fire gas pressures for the boiler being fired.
Fit a manometer (suitable for 30mbar) onto manifold
test point.
Light the boiler, then remove the protective cover from
the Hi/Lo pressure regulator.
To adjust the high fire gas pressure, turn the outer nut
on the hi/lo pressure regulator.
To adjust low fire/start gas pressure, remove the link
between terminals C3 and C4; nominally set the low
fire/start gas pressure by rotating the inner cross-
head screw, whilst keeping the outer nut from
rotating. Turn the boiler off then on again and fine
trim the pressure.
Insert or make high fire link on terminals C3 and C4;
the boiler should now drive to high fire. Replace
protective cap on Hi/Lo gas valve.
Note! The low fire setting must always be set last
of all. The valves operation may be incorrect if
this omitted.
Note!
It is also advisable to carry out this procedure
with all the boilers firing. The long-term reliability of
the ignition system may well be reduced unless this
procedure is carried out correctly.
Содержание Purewell
Страница 4: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G ii THIS PAGE LEFT INTENTIONALLY BLANK ...
Страница 19: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G 13 Figure No 7a Exploded View of Casing Set ...
Страница 28: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G 22 Figure No 10 General Layout Front View ...
Страница 40: ...HAMWORTHY HEATING LTD PUREWELL AUTOMATIC IGNITION 500001035 G 34 THIS PAGE LEFT INTENTIONALLY BLANK ...