• Use the Total and Clean keys to browse through the parameter names, and to modify the
parameter value
• 3-second long press of On/Off key to end the Low-level programming mode and exit back
to previous mode. However, there is also a 30-second timeout, so that if no key pressed
for that time, the unit resumes operation on its own.
There is a special key sequence that allows resetting the Low-level parameters to their factory de-
faults described here. During power-up, if the Clean key is pressed, the unit will reset all parameters
to their default values.
MAXIMUM UV CLEAN TIME
Maximum time allowed (in kilo-hours) before UV Service LED lights.
Parameter name: P01
Allowed values:
0.01 to 9.99
Factory default:
1.60
MAXIMUM UV OPERATING TIME
Maximum time allowed (in kilo-hours) before UV Service LED lights.
Parameter name: P02
Allowed values:
0.01 to 9.99
Factory default:
9.99
FAN TURN-OFF DELAY
When unit is turned Off, fans remain on for a certain period (seconds) until residual ozone is
evacuated.
Parameter name: P03
Allowed values:
0 (immediate) to 999
Factory default:
30
FAN OPERATION DURING FIRE
When unit detects the Fire input, it shuts off the UV Lamp output. Fans are also shut off according
to this parameter.