Instruction Manual PSx3xxPL
13
2.8
Start-up
After the supply voltage has been hooked up, a positioning or manual run can begin
immediately.
For the start-up of the STO safety function see separate safety manual
(Document No. 7100.006654).
2.8.1 Positioning run
- To be able to control the drive with the help of PDOs, it has to be switched to the CN
cycle state “operational”.
- Transfer target value:
- PDO with control word = 0x14 and desired target value
OR
- PDO with control word = 0x10 and target value in SDO #2001
Drive begins run
- Abort run by resetting the release bit:
- PDO with control word = 0x00
OR
- SDO #2024 with value 0x00 (if pre-operational)
- If a new target value is transferred during a positioning run, the device will
immediately proceed to the new target. There will be no interruption if the direction of
rotation does not need to be altered.
- If a manual run is transmitted during a positioning run, the positioning run will be
aborted (speed will be reduced to that of a manual run) and the device proceeds with
the manual run.
The following sequence of steps is also possible:
Starting situation: release has not been set
- Transfer target value:
- PDO with control word = 0x04 and desired target value
OR
- PDO with control word = 0x00 and target value in SDO #2001
- Set release:
- PDO with control word = 0x10
OR
- SDO #2024 with value 0x10 (if pre-operational)
Drive begins run
Where applicable, positioning runs involve a “loop run” which causes the target
position to be reached from a predefined direction. The direction and the length
of the loop run
can be set to the desired value with SDO #201F (“length of loop”)
before the run. With SDO #201F the loop run might also be disabled
.
Underwater usage of the PSW is not allowed
Setting of control word and target value with the help of SDOs is only possible in
the CN cycle state “pre-operational”.