Instruction Manual PSx3xxIO
9
2.6 IO-Link
For the IO-Link interface, IEC 61131-9 Version 1.1.2 is used as the SDCI protocol.
The format of the output data can be optionally constructed according to the time
stamp specification from the company Sick (consisting of a time stamp and two
control bits), or consist of a control word and target value (process data; this is the
delivery condition).
(a) Table of the implemented object directory entries
Designation
ISDU
Number
Function
Value
range
Secu
red
Deli
very
R/W
IO-Link standard variables
Direct
Parameter 1
0
Sub 1: Master command
Sub 2: Master cycle time
Sub 3: Minimum cycle time
Sub 4: M-Sequence Capability
Sub 5: IO-Link version ID
Sub 6: Process data input length
Sub 7: Process data output length
Sub 8: Vendor ID 1
Sub 9: Vendor ID 1
Sub 10: Device ID 1
Sub 11: Device ID 2
Sub 12: Device ID 3
Sub 13: reserved
Sub 14: reserved
Sub 15: reserved
Sub 16: Standard command
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
8 bit
68
43
17
135
16
2
216
0
0
0
W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
W
Standard
command
2
To trigger specific commands
8 bit
W
Value
128
130
160
161
Meaning
Reset device
Restore factory setting
Restore factory setting without
changing the process data format
Save the parameters in EEPROM
Содержание PS*3**IO series