b)
Ensure that all (inner and outer tube) sealing rings are provided and
assemble the air/flue ducts as shown in the flue instructions.
c)
Construct the correct flue length by building the flue out from the
appliance.
Ensure that the flue and air seals are correctly fitted
before assembly and that each section is fully engaged.
The flue length is measured from the centreline of
the appliance flue outlet to the inside of the external
wall-sealing ring. In most cases it will be possible to
achieve the required flue length without cutting the
ducts, however where necessary the plain ends of
the extension ducts may be cut. Never cut the
swaged end, and always ensure that the cut is square
and free of burrs or debris.
NOTE IT IS ESSENTIAL THAT THE TERMINAL IS
FITTED THE CORRECT WAY UP.
See flue kit Instructions (i.e. rain shield at the top).
13
MEASURING THE EXACT FLUE LENGTH
WALL
FAN OUTLET
EXTERNAL
Dia. 60mm
L
TOTAL FLUE LENGTH
FROM OUTLET CENTRE
TO OUTSIDE WALL FACE:
= LENGTH
L
14
FIBRE
SEAL FITTED
INTERNAL WALL
SEALING RING
130mm Dia.
HOLE WITH
WALL LINER
TOP
EXTERNAL WALL
SEALING RING
1
INSERT
ASSEMBLED
FLUE SYSTEM
FROM INSIDE
THE ROOM.
EXTERNAL
WALL
SEALING RING
OPENS
2
ALIGN ASSEMBLED FLUE
SYSTEM ELBOW TO
APPLIANCE AND SECURE
3
SLIDE
INTERNAL
WALL
SEALING RING
TO WALL TO
FORM A GOOD
SEAL
INSTALLING THE FLUE SYSTEM FROM
INSIDE THE ROOM
INSTALLING THE AIR/FLUE DUCT
FROM INSIDE THE ROOM
4.7.1
Wall thickness up to 800 mm (31in) only.
a)
Push the terminal through the wall liner taking care to ensure that
the terminal is the correct way round and the external wall-sealing
ring does not become dislodged.
b)
Assemble the flue system extension ducts as necessary, referring
to Figure 14.
c)
Pull the flue system towards the appliance to seat the external
sealing ring against the outside wall, ensuring that the duct joints
are not disturbed.
d)
Use the internal sealing ring to make good the internal hole, and
check that the terminal is correctly located on the outside wall
(Where possible this should be visually checked from outside the
building.) Figure 14 shows a view of the flue system, correctly
installed.
e)
Finally locate and secure the elbow to the appliance using the four
screws provided.
INSTALLING THE AIR/FLUE DUCT
FROM OUTSIDE THE BUILDING
4.7.2
(Flue hole diameter 100 mm - wall liner not necessary)
a)
Secure the flue elbow with seal to the appliance using 4 screws.
b)
Fit external wall sealing ring over flue and then from outside the
building, push the flue system through the wall taking care to
ensure that the terminal is the correct way around.
c)
Loosely fit the internal wall sealing ring over the inside end of the
flue.
d)
Assemble the flue system extension ducts as necessary, referring
to the flue kit instructions, and fit to the flue elbow.
e)
Fit the flue terminal to the flue system, ensuring that the duct joints
are not disturbed, and that the external sealing ring is seated
against the outside wall.
f)
Finally use the internal sealing ring to make good the internal hole.
Check that the external wall sealing ring and the terminal is
correctly located, on the outside wall from outside the building.
18
SINGLE PAGES 20/9/10 10:00 Page 20
Содержание EDEN X Type VBX 30
Страница 29: ...27 7 INTERNAL WIRING DIAGRAMS 31 7 1 FUNCTIONAL FLOW WIRING DIAGRAM SINGLE PAGES 20 9 10 10 00 Page 29...
Страница 40: ...51 1 5 9 2 6 10 3 7 11 4 8 12 38 SINGLE PAGES 20 9 10 10 01 Page 40...
Страница 41: ...SINGLE PAGES 20 9 10 10 01 Page 41...
Страница 42: ...SINGLE PAGES 20 9 10 10 01 Page 42...