Super Match
4.The circle flashes where the cursor locates when choosing static pressure and rated value; if the cursor moves
to wired controller group No. location, the No. will be underlined and the range of No. is 1-16.
• Detailed information
(the common user password is required for access)
1. Proceed through main interface→Menu→other→enter the password→Details→press "Enter" to initiate.
2. 063 is the address of the wired controller inside the group; if one unit is controlled by one wired controller, the
default address is 01; the range of this value is 01 to 16; the Indoor address is the communication address of
both indoor unit and outdoor unit, ranging from 1 to 64.
3.The wired controller address equals the corresponding value of indoor unit's group address dial code plus 1.
• State setting
(this function is intended for debugging by technical personnel and can be entered by high-class users only)
1. Proceed through main interface→Menu→Other→enter the high-class user password→Status set→press
"Enter" to initiate.
2. Use the upward, downward, leftward and rightward keys to adjust the cursor; the location where the cursor
stays has the circle flickering; press "Enter" key to change it to
, and the setting is completed. indicates
"Selected" and indicates "Unselected"
3. Auto recovery: if this function is on, the state before power failure will be in the memory; after restoration of
power failure, the unit will continue operating in the state as before the power failure. If this function is off, the
state will not be memorized; if the unit is energized after power failure, it is in shutdown state; after startup, the
default mode is in automatic mode as automatic air 24*. If the auto recovery is set to be on and the sleep function
is also set, in case of accidental power failure, the unit is in shutdown state when the power supply is resumed.
4. Master/slave setting: This setting is used for master/slave control of the wired controller and the master
controller and slave controller are set separately.
5. Unit of temperature: Temperature is set in the units of Celsius degree and Fahrenheit degree.
Operation
161