GRUPAd.o.o.
24
10
2
SW9
SW10
SW11
function
description
11
2
6
6
outdoor compulsory cooling
mode in rated condition
press START for 2 seconds, display COOL to enter
cooling mode, inverter control begins. Press STOP
for 2 seconds, display --. Outdoor rated operation
frequency is 80Hz, the other is automatical control.
Outdoor frequency will not change according to indoor
capacity.
outdoor compulsory heating
mode in rated condition
press START for 2 seconds, display HEAT to enter
heating mode, inverter control begins. Press STOP
for 2 seconds, display --. Outdoor rated operation
frequency is 80Hz, the other is automatical control.
Outdoor frequency will not change according to indoor
capacity.
WARNING: In the above table, 6, 8, 2/6, 9, 2/6, 10, 2/6, 11, 2 are FORBIDDEN TO BE USED IN
DEBUGGING.