GRUPAd.o.o.
14
2.8 Confirm the indoor control type
N. Wired control/remote control selection: SW08-6
SW08-6
1
0
wired control type
remote control type
function
Control method Wired control master unit Wired control slave unit Remote control unit
Socket
/jumper
CN23 short connected disconnected disconnected
CN30 short connected short connected disconnected
CN21 blank blank to remote receiver
SW08-[6] ON ON OFF
signal terminal block A,B,C to B,C to A,B,C not
wired controller wired controller to wired controller
2.9 Confirm the indoor communication address when in central control: SW03 on
indoor PCB
SW03 on indoor PCB
1: ON
0: OFF