W
arnings:
A. Do not take the other wire except fo
r copper wire as the power cable.
B. All indoor/outdoor units must be con
nected with the earthing wire of power
cable. The earthing wire can not be co
nnected onto the earthing wire of coal
gas pipe, water pipe, lightning rod, or t
elephone. Or the electric shock or fire
will occur
.
C. Must install the leakage breaker and
the over current breaker
, or electric
shock will occur
.
D. Before finishing electric installation,
do not electrify the unit.
E. Indoor and outdoor use their individ
ual power source. All indoors use one
power source.
F. The communication wire and the po
wer cable must be individual and can
not use one multi-core cable, or the co
mmunication wire will be interfered to
cause abnormal.
leakage breaker
over circuit breaker
leakage breaker
over circuit breaker
leakage breaker
over circuit breaker
leakage breaker
over circuit breaker
leakage breaker
over circuit breaker
leakage breaker
over circuit breaker
2-core wire(communication)
2-core wire(communication)
2-core wire(communication)
2-core wire(communication)
main switch
main switch
2-core wire(power supply)
2-core wire(power supply)
2-core wire
(power supply)
power supply
power supply
2-core wire
(power supply)
2-core wire
(power supply)
switch
switch
switch
L N
L N
L N
L N
switch
L N
switch
L1 L2 L3 N
L1 L2 L3 N
Outdoor unit
Indoor unit
AV08~16NMVERA and its indoor units
=UQVP `U[UXS
4.
109