background image

Outdoor unit

1.Connection of pipes

2.Attaching Drain-Elbow

To bend a pipe, give the roundness as large as possible not to crush the pipe
Connecting the pipe of gas side first makes working easier.
The max vertical distance between the indoor unit and the outdoor unit is 5 m.

 If the drain-elbow is used, please attach it as
 figure. (Note: Only for heat pump unit.)

Half union

Flare nut

Spanner

Torque wrench

4

Outdoor unit

Forced fastening without careful centering
may damage the threads and cause a
leakage of gas.

Be careful that matters, such as wastes of sands, etc. 
shall not enter the pipe.

3.Purging Method:

Push the air out of the indoor unit and piping as followes:

Tighten the caps on the valves with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k

24k) refrigerant shall be 

 added per exceeding meter. Charge according to the following list. 

Piping length

Additional amount

5m

7m

No need

40g

10m

100g

for 5k 7k 9k 10k 12k 13k 18k

for  22k 24k 

Max. Length:       for 5K 7K 9K 10K: A=7m
                            for 12K 13K:

 A=10m

                            for 18K 22K 24K:   A=20m

Max.Elevation:

for  5K 7K 9K 10K 12K 13K: B=5m

for 18K 22K 24K: B=10m

Piping length

Additional amount

5m

7m

No need

120g

10m

300g

20m

900g

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

B

A

C

Outdoor unit

Indoor unit

Oil trap

A

B

CAUTION
In case more than 5 metres

ˈ

oil trap

should be installed every 5~7m.

C

Pipe Diameter   (     )

Liquid side  6.35mm(1/4")

Gas side  9.52mm(3/8")

Fastening torque

18N.m

40N.m

Gas side  12.7mm(1/2")

50N.m

Gas side  15.88mm(5/8")

60N.m

Liquid side  9.52mm(3/8")

 40N.m