45
S/N Fault code
Fault description
Remarks
43
E70
Overtemperature of suction temperature sensor of System A compressor
▲
44
E71
Overtemperature of suction temperature sensor of System B compressor
▲
45
E72
Overtop Temperature difference of in and out water
*
46
E74
Over-current protection of System C compressor
▲
47
E75
Open circuit or short circuit in exhaust temperature sensor of System C
compressor
√
48
E76
Open circuit or short circuit in coil (outlet) temperature sensor 1 of System C
√
49
E77
Open circuit in low-pressure sensor of System C
√
50
E78
Low pressure protection of System C
▲
51
E79
Open circuit or short circuit in suction temperature sensor of System C
√
52
E80
Running time exceeded
*
53
E81
Overtemperature of exhaust temperature sensor of System C compressor
▲
54
E82
Overtemperature of coil (outlet) temperature sensor 1 of System C
√
55
E83
High-pressure protection of System C
▲
56
E87
High-pressure protection of System D
▲
57
E89
Over-current protection of System D compressor
▲
58
E90
Open circuit or short circuit in exhaust temperature sensor of System D
compressor
√
59
E91
Open circuit or short circuit in coil (outlet) temperature sensor 1 of System D
√
60
E92
Open circuit in low-pressure sensor of System D
√
61
E93
Low pressure protection of System D
▲
62
E94
Open circuit or short circuit in suction temperature sensor of System D
√
63
E96
Overtemperature of exhaust temperature sensor of System D compressor
▲
64
E97
Overtemperature of coil (outlet) temperature sensor 1 of System D
√
Note:
*, Once this error occurs,need according to the troubleshooting to remove the cause of failure
and then to electricity back on.
▲,They are severe protection faults.If such faults are repeated three times within 60min, the
corresponding automatic recovery,and they must be recovered after troubleshooting in power
failure.
√ ,can be automatically restored after trouble
1. If the master unit malfunctions, the master unit stops, without impact on other units (except
for flow switch fault).
2. If the slave unit malfunctions, only this unit stops, without impact on other units.
Содержание CA0035EAND
Страница 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Страница 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Страница 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Страница 13: ...11 5 Refrigerant system diagram HPs dry evaporator 4wv TXV Tewo Tewi heat exchanger Td Ps Ts Tdef1 Tdef2 ...
Страница 37: ...35 8 Wiring Diagram ...
Страница 38: ...36 ...
Страница 39: ...37 ...
Страница 40: ...38 ...