6.2 Site requirements
1) Noise considerations
■
The unit is placed in the non-noise sensitive areas
■
The damping pad on the unit below (not supplied with the standard model damping pad, user-owned)
■
Install rubber shock absorbers on all water pipeline
■
Seal all wall gap at room
Note demanding applications should consult an acoustic engineer
2) Ground
Install it on a hard, easy deformation of mounting pads or a concrete foundation to withstand the total weight of
the living unit at runtime (including all piping, refrigerant, oil, water).
Referring operating weight parameter table. After placing a good unit, machine leader and level of assurance
in the width direction should 1/4 "(6.35mm) within. Haier company equipment problems as the basis of design
or construction caused inappropriate will not take any responsibility.
3) Shock absorbers
■
Provide rubber shock absorbers for the unit all the water pipes (Haier company standard models do not random
with shock absorbers, user-owned).
■
Use a flexible tube connecting wire electrical lines.
■
Isolate all pipe hanger to ensure that they are not supported by the main structural beams of the building, so as
to avoid vibration transmitted live and work areas.
■
Ensure that the pipeline will not add additional pressure to the unit.
Be careful not to use metal tube shock absorbers, because the frequency range of plant operation, the damper
is ineffective.
4) Frost protection
Note
In the case of low ambient temperature in winter, overnight shutdown period, heat exchangers and water pipes
may freeze inside, causing damage to equipment and piping. To prevent freezing, never allow the unit off
(because the unit has an automatic antifreeze function), as well as possible icing must put all the water
discharge pipe; hot side 65 to increase drainage and air-conditioned sides need to water line installation valve,
care must be taken to be installed at the lowest point of the water circuit, if the drainage more difficult case, you
can use anti-freeze mixture of ethylene glycol or propylene glycol (ratio table below).
Freezing and boiling points of ethylene glycol solution (anti-freeze glycol concentration table):
Freezing point
°C
Glycol
concentrations%
Density (20°C)mg/
cm³
Freezing point °C
Glycol
concentrations%
Density (20°C)mg/
cm³
-10
28.4
1.034
-40
54
1.0713
-15
32.8
1.0426
-45
57
1.0746
-20
38.5
1.0506
-50
59
1.0786
-25
45.3
1.0586
-45
80
1.0958
-30
47.8
1.0627
-30
85
1.1001
-35
50
1.0671
-13
100
1.113
Содержание CA0035EAND
Страница 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Страница 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Страница 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Страница 13: ...11 5 Refrigerant system diagram HPs dry evaporator 4wv TXV Tewo Tewi heat exchanger Td Ps Ts Tdef1 Tdef2 ...
Страница 37: ...35 8 Wiring Diagram ...
Страница 38: ...36 ...
Страница 39: ...37 ...
Страница 40: ...38 ...