Service Diagnosis
3
8
10.4.7
The communication fault between IPM and outdoor PCB
Outdoor display:
F3 LED1 flash 4 times
Communication is detected by checking the IPM module and the outdoor PCB
■ The outdoor PCB broken leads to communication fault
■ The IPM module broken leads to communication fault
■ The outdoor PCB is broken
■ The IPM module is broken
■
Communication wiring disconnected
* Caution: Be sure to turn off power switch before connect or disconnect connector,
or else parts damage may be occurred.
Method of
Malfunction
Detection
Trouble
shooting
Supposed
Causes
Malfunction
Decision
Conditions
Are they good?
Pull out and reinsert the terminals.
Replace connected wire
Replace the outdoor PCB with a new
one
Replace the outdoor IPM
module with a new one.
Check whether the CN23 and CN24
terminals of the outdoor PCB and the
CN10 and CN11 terminals of the IPM
module are tightly connected.
Check whether the connection between
the power module and the outdoor P&N
line is tight
Electrify the machine again and turn it on.
Check whether the voltage between 1 and 2
of Terminal CN23 is about DC5V.
Check whether the voltage between2 and 3
of terminal CN23 is about DC15V.
NO
YES
Malfunction unsolved
NO
1 2 3
Содержание AS35RBAHRA-PL
Страница 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 9 52CuT 9 52CuT 6 35CuT 6 35CuT...
Страница 15: ...Printed circuit board connector wiring diagram 13 Domestic air conditioner Wiring diagrams...
Страница 50: ...Circuit diagrams 49 Domestic air conditioner 11 Circuit Diagrams...
Страница 51: ...Circuit diagrams 50 Domestic air conditioner...
Страница 55: ...three 6 Removal Procedure 54 Domestic Air Conditioner Remove the casing 1 2 3...
Страница 59: ...Removal Procedure 58 Domestic Air Conditioner motor cover motor cover...
Страница 60: ...Removal Procedure 59 Domestic Air Conditioner...