Service Diagnosis
34
10.4.4
Outdoor DC fan motor fault
Outdoor display F8 LED1 flash 9 times
DC fan motor is detected by checking the fan running condition and so on
When the detected rotation feedback signal don’t received in2 minutes
■ DC fan motor protection dues to the DC fan motor faulty
■ DC fan motor protection dues to faulty PCB
* Caution: Be sure to turn off power switch before connect or disconnect connector,
or else parts damage may be occurred.
Method of
Detection
Trouble
shooting
Supposed
Causes
Malfunction
Decision
Conditions
Check whether terminal
on the outdoor mainboard
is well inserted.
It is normal
NO
Reinsert the terminal
YES
Electrify the machine again and
turn it on in the cooling state with
the remote control. Check
whether the motor could run
.
YES
The motor and outdoor PCB
are well
NO
Remove fan motor after switch off
the power. Measure the
resistances between black line
and red line, between black line
and white line of the fan motor
Содержание AS35RBAHRA-PL
Страница 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 9 52CuT 9 52CuT 6 35CuT 6 35CuT...
Страница 15: ...Printed circuit board connector wiring diagram 13 Domestic air conditioner Wiring diagrams...
Страница 50: ...Circuit diagrams 49 Domestic air conditioner 11 Circuit Diagrams...
Страница 51: ...Circuit diagrams 50 Domestic air conditioner...
Страница 55: ...three 6 Removal Procedure 54 Domestic Air Conditioner Remove the casing 1 2 3...
Страница 59: ...Removal Procedure 58 Domestic Air Conditioner motor cover motor cover...
Страница 60: ...Removal Procedure 59 Domestic Air Conditioner...