Functions and control

18 

Domestic air conditioner 

7.1.9    Dormant operation

The dormant timing is an eight hours unadaptable one. The timing signs are shown on the V series 
board. (RC series show the dormant signal, the timing light is lighted on the 6 lights board). 
2.1 Under the cooling/ dehumidifying operation, after the setting of the dormant operation, the set 
temperature will be raised for 1 centigrade after 1 hour’s operation and will be raised for 1 centigrade 
1 hour later. The system will keep this status for 6 hours and then close. 
2.2 Under the heating mode, after the setting of the dormant operation, the setting temperature will fall 
2 centigrade after 1 hour’s operation and will fall 2 centigrade 1 hour later. 3 hours after the preceding 
operations, the set temperature will be raised for 1 centigrade and the system will keep this status for 
3 hours and then close down. 
2.3 During the dormant time, except the change of the system mode or a new press on the dormant 
setting keys, the timing of the 8 hours dormancy will take the first timing as the start time, any presses 
on other keys will not affect the original timing. 
2.4 Indoor fan control under the dormant operation. 
If the indoor fan is at the high speed before the dormant operation setting, the speed will be turned to 
medium after the setting. If the fan is at the medium speed before the dormant setting, the speed will 
be turned to low after the setting. If the fan is at the low speed before the dormant setting, the speed 
will not change. 

7.1.10 Urgent on/off input 

Press the urgency button the buzzer will ring. The system will enter the automatic mode if you don’t 
press the button for more than 5 seconds. 
Under the system off mode, if you press the urgency key for 5 to 10 seconds, the system will start the 
test operation. 
Under the system off mode, if you press the urgency key for 10 to 15 seconds, the display screen will 
show the resume of the last malfunction. 
If the system is under operation, the press on the urgency key will stop it. 
Under the system off mode, the display screen will show automatic running sign. 
Under the system off mode, the system will not receive the remote control signal if the press on the 
urgency key doesn’t last for 15 seconds or if the key is loosened.   
Urgency operation: If you press the urgency key for less than 5 seconds, the buzzer will ring when you 
press the on/off key. The system will enter the urgency operation when the urgency key is loosened. 
The urgency operation is fully automatic. 
Test operation. 
The inlet temperature sensor doesn’t work, the indoor fan and the indoor air direction board motor 
works  synchronically.  High  speed  airflow,  cooling,  outdoor  system  on,  etc,  will  send  the  ambient 
temperature 30 centigrade and coil temperature 16 centigrade information to the outdoor system. 
Test operation 
The defrost protection of the evaporator doesn’t work. 
The temperature control doesn’t work. 
The test operation will be finished in 30 minutes. 
The test operation can be stopped by the relative commands from the remote control. 

Содержание AS35RBAHRA-PL

Страница 1: ...on s to advise non technic al individuals of potentia l dangers in attemptin g to servic e a product Product s powered by electricit y should be service d or repaire d only by experience d professiona...

Страница 2: ...2 Features 7 3 Specifications 8 4 Sensors list 9 5 Piping diagrams 10 6 Printed circuit board connector wiring diagram 11 7 Functions and control 8 Dimensional drawings 9 Center of gravity 10 Service...

Страница 3: ...1 1 Model Nameplate A S 3 5 R B A H R A Apply toT1 220 240V50HZ 1ph DC inverter Indoor units Version number 35 capacity Platform of indoor units R R platform Nominal cooling capacity 11945BTU h Type...

Страница 4: ...est operation to ensure that the equipment operates Normally and explain the cautions for operating the product to the customer Check the embedded wire are four roots L N COM GND GND is needed if not...

Страница 5: ...n cause an electrical shock or fire Warning Do not repair the electrical components with wet hands Working on the equipment with wet hands can cause an electrical shock Do not clean the air conditione...

Страница 6: ...r electrical work can cause an electrical shock or fire Be sure to use the specified cable to connect between the indoor and outdoor units Make the connections securely and route the cable properly so...

Страница 7: ...mains around the unit it can cause a fire Be sure to install the packing and seal on the installation frame properly If the packing and seal are not installed properly water can enter the room and wet...

Страница 8: ...ck Be sure to check the drainage of the indoor unit after the repair Faulty drainage can cause the water to enter the room and wet the furniture and floor 1 2 4 Using Icons Icons are used to attract t...

Страница 9: ...equency It enables users to enioy a cool room within a much shorter time micro particles including dust virus and bacteria to provide healthier environment Strong Airflow With improved fan and air duc...

Страница 10: ...W W P O C S R E E S 184 h W K n o i t p m u s n o c y g r e n e l a u n n A h m l a v o m e R e r u t s i o M TECHNICAL SPECIFICATIONS m m D W H s n o i s n e m i D m s n o i s n e m i D d e g a k c a...

Страница 11: ...t a r e p m e t r o t a r o p a v e d n a m R o o r g n i t c e t e d Conversation formulae Kcal h KW 860 Btu h KW 3414 cfm m min 35 3 Specifications TECHNICAL SPECIFICATIONS PARTS cooling heating Typ...

Страница 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 9 52CuT 9 52CuT 6 35CuT 6 35CuT...

Страница 13: ...control Pin 3 and Pin 4 combined control corresponding to 23 26 33and35of the machine respectively 2 Jumper J1 and J2 combined control corresponding to different series of display boards ON means kee...

Страница 14: ...estic air conditioner PCB 1 PE L N Ion generator ACFan motor Anion module Ambient Pipe Temp sensor Room card Display board Emergency Up down stepmotor Right left stepmotor Human light sensors controll...

Страница 15: ...Printed circuit board connector wiring diagram 13 Domestic air conditioner Wiring diagrams...

Страница 16: ...Backlash B the compressor will be shutted the indoor fan will operate at the set speed and the mode signal will be sent to the outdoor system The system will keep the original status if Tr Ts Airflow...

Страница 17: ...opped for more than 3 minutes and the outdoor system still operates the system will be changed into light speed mode When the airflow speed has no delay from the high to low switching the speed should...

Страница 18: ...ayed for 3 minutes remain at high speed for 3 minutes before the next switch Airgate location control the location for the airgate can be set according to your needs Coldair proof operation 1 The fan...

Страница 19: ...ration 7 1 7 Air refreshing This model does not choose After receiving the signal from the remote control HV series the background light of the health logo is green HS series the health indicator will...

Страница 20: ...tting If the fan is at the low speed before the dormant setting the speed will not change 7 1 10 Urgent on off input Press the urgency button the buzzer will ring The system will enter the automatic m...

Страница 21: ...system When the outdoor system operates if the indoor system operation differs from the outdoor system the abnormal operation malfunction will be reported 10s after the report the indoor system will...

Страница 22: ...indoor system thus can quit the single operation mode 7 1 17 Power cut compensation Entering condition Press dormant button 10 times within 7 second the buzzer will ring 4 times and the present syste...

Страница 23: ...62 0907 1 68 1 55 15 70 0342 64 3023 58 9863 1 66 1 54 14 66 3463 61 0123 56 0565 1 64 1 52 13 62 8755 57 9110 53 2905 1 62 1 51 12 59 6076 54 9866 50 6781 1 60 1 49 11 56 5296 52 2278 48 2099 1 58 1...

Страница 24: ...7475 10 4216 10 0964 0 75 0 75 25 10 3000 10 0000 9 7000 0 75 0 75 26 9 8975 9 5974 9 2980 0 76 0 76 27 9 5129 9 2132 8 9148 0 80 0 80 28 9 1454 8 8465 8 5496 0 84 0 83 29 8 7942 8 4964 8 2013 0 87 0...

Страница 25: ...2 29 68 2 2347 2 0695 1 9147 2 49 2 34 69 2 1652 2 0032 1 8516 2 54 2 38 70 2 0983 1 9393 1 7908 2 59 2 42 71 2 0337 1 8778 1 7324 2 63 2 46 72 1 9714 1 8186 1 6761 2 68 2 50 73 1 9113 1 7614 1 6219...

Страница 26: ...0 6484 4 29 3 88 104 0 7848 0 7036 0 6303 4 34 3 92 105 0 7641 0 6845 0 6127 4 40 3 97 106 0 7441 0 6661 0 5957 4 46 4 02 107 0 7247 0 6482 0 5792 4 51 4 07 108 0 7059 0 6308 0 5632 4 57 4 12 109 0 68...

Страница 27: ...Service diagnosis Domestic air conditioner 26 8 Dimensional unit mm 9 Center of gravity unit mm 292 805 199 501 6 805 292 128 805 310 199 95...

Страница 28: ...CB is broken Operation sometimes stops Check the power supply A power failure of 2 to 10 cycles can stop air conditioner operation Equipment operates but does not cool or does not heat only for heat p...

Страница 29: ...21 Indoor unit overload in heating mode pipe temperature sensor Indoor PCB Indoor motor E14 Indoor fan motor malfunction Indoor motor Indoor PCB Outdoor Malfunction F1 2 IPM protection Power module Re...

Страница 30: ...frigerant compressor F23 25 Compressor U phase overcurrent Compressor V phase overcurrent Compressor W phase overcurrent Power module Refrigerant compressor F24 27 CT detection current abnormal protec...

Страница 31: ...ssor operation Note The values vary slightly in some models Faulty connector connection Faulty thermistor Faulty PCB Caution Be sure to turn off power switch before connect or disconnect connector or...

Страница 32: ...h 1 times The Data detected by the EEPROM are used to determine MCU When the data of EEPROM is error or the EEPROM is damaged Faulty EEPROM data Faulty EEPROM Faulty PCB Caution Be sure to turn off po...

Страница 33: ...es Detection error due to faulty indoor unit PCB Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Trouble shooting Method of Malfunc...

Страница 34: ...check if the motor can run YES Measure whether there is a voltage pulse 0 15VDC between 4 and 5 of the CN9 terminal on the indoor PCB The indoor motor is damaged and need replace NO Is it ok YES The...

Страница 35: ...ore connect or disconnect connector or else parts damage may be occurred Method of Detection Trouble shooting Supposed Causes Malfunction Decision Conditions Check whether terminal on the outdoor main...

Страница 36: ...ck line and red line between black line and white line of the fan terminal of outdoor PCB are greater than 10M YES The module PCB is damaged replace it with a new one The motor of the outdoor unit is...

Страница 37: ...ecision Conditions Method of Malfunction Detection Trouble shooting Electrify the machine again and turn it on with the remote control If malfunctions are reported before or upon the compressor being...

Страница 38: ...s damage may be occurred Malfunction Decision Conditions Method of Malfunction Detection Trouble shooting Supposed Causes The system may have been over or under charged with gas which can be judged th...

Страница 39: ...hod of Malfunction Detection Trouble shooting Supposed Causes Malfunction Decision Conditions Are they good Pull out and reinsert the terminals Replace connected wire Replace the outdoor PCB with a ne...

Страница 40: ...h before connect or disconnect connector or else parts damage may be occurred Supposed Causes Malfunction Decision Conditions Method of Malfunction Detection Trouble shooting Is it ok Test the outdoor...

Страница 41: ...sion Conditions Method of Malfunction Detection The temperature exceeds 110 shortly after the machine starts up The cryogen may have been leaked during installation or there may be leakage in the pipi...

Страница 42: ...is broken Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Supposed Causes Malfunction Decision Conditions Method of Malfunction De...

Страница 43: ...hen only indoor charged The indoor PCB is damaged replace it with a new one Test the outdoor power is supply 230VAC with a universal meter when indoor and outdoor are charged Check the cable between o...

Страница 44: ...an motor terminal resistance between pin 1 310V and pin 4 0V or pin 5 15V and pin 4 0V of CN21 are close to 0m with a universal meter after switch off the power NO Remove the connection cable between...

Страница 45: ...ower switch before connect or disconnect connector or else parts damage may be occurred The outdoor PCB needs dehumidification Is it normal after restart the AC If starting up normally but malfunction...

Страница 46: ...hite line is not close to18V DC when only indoor charged YES The indoor PCB is damaged replace it with a new one NO Test the outdoor power is supply 230VAC with a universal meter when indoor and outdo...

Страница 47: ...tart the unit the LED 2 becomes light or flash Fan motor is damaged Replace it with a new one YES NO Test the fan motor terminal resistance between pin 1 310V and pin 4 0V or pin5 15V and pin4 0V of C...

Страница 48: ...onnector or parts damage may be occurred Conditions Decision Malfunction Method of Malfunction Detection Trouble shooting Malfunction unsolved Maybe there is some disturbance Malfunctions exist also t...

Страница 49: ...e to turn off power switch before connect or disconnect connector or parts damage may be occurred Trouble shooting Supposed Causes Malfunction Decision Conditions Method of Malfunction Detection The m...

Страница 50: ...Circuit diagrams 49 Domestic air conditioner 11 Circuit Diagrams...

Страница 51: ...Circuit diagrams 50 Domestic air conditioner...

Страница 52: ...Removal Procedure 51 Domestic Air Conditioner Removal of front panel front panel Remove the foam cushion 2 Loosen the screw 12 Removal Procedure...

Страница 53: ...Removal Procedure 52 Domestic Air Conditioner Lift up the control box cover 3 Loosen the screw 4 Lift up the control box cover 5...

Страница 54: ...n release the pivots on both sides of the unit to remove the front panel Removal of front panel Removal Procedure 53 Domestic Air Conditioner Pull the wires out of the control box 6 Remove the air fil...

Страница 55: ...three 6 Removal Procedure 54 Domestic Air Conditioner Remove the casing 1 2 3...

Страница 56: ...horizontal flap flap Removal Procedure 55 Domestic Air Conditioner and the stepper motor Loosen the screws and remove the stepper motor...

Страница 57: ...2 Every blade go round and round then move it Removal Procedure 56 Domestic Air Conditioner horizontal louver and control box Loosen the screws...

Страница 58: ...3 57 Domestic Air Conditioner Removal Procedure Loosen the hook and the service Cover Lift up the exchanger and remove it...

Страница 59: ...Removal Procedure 58 Domestic Air Conditioner motor cover motor cover...

Страница 60: ...Removal Procedure 59 Domestic Air Conditioner...