sensor abnormal
short circuit for more than
2m continuously
13 0D 31D
Solenoid valve
abnormal
Solenoid valve act
incorrectly 3 times
continuously
○
14 4C 15D
Discharging
temp.
sensor abnormal
Sensor broken down or
short circuit for more than
2m continuously
○
15
05
17D
EEPROM abnormal
EEPROM data missing
Run as the
default
value
16 54 26D
Pressure
abnormal(low
pressure)
Low pressure switch acts in
normal running
○
17 50 15D
Compressor
overheat
the
discharging
temperature is higher than
120degree
Resumable
if lower
than
100degree
18
0C
23D
Abnormal mode
Indoor operation mode is
different with the running
indoor unit.
○
19 4B 18D
Outdoor coil
B(suction temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
○
20 4D 15D
Outdoor
discharging
B(oil temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
○
21
32
07D
Power module failure Power module overheat, or
over current, or short circuit
※
22 54 08D
Outdoor DC fan motor
failure
※
○
shows resumable fault,
※
shows it is not resumable fault.
Setting address method:
The address setting can be realized by setting indoor PCB.
If you use the group control function, there should be a master unit and 15 sets of slave units.
For the master unit, the SW5-3 should be at “ON”. For the slave units, the SW5-3 should be
at “OFF”.
Please refer the below table,
Indoor
unit
address
SW1-4 SW1-3 SW1-2 SW1-1
1 OFF OFF OFF OFF
2 OFF OFF OFF ON
-49-