Commercial Air Conditioner
Model: AU182AFERA
AD182AMERA, AS182AVERA
g Preset
―――
H
Outdoor total capacity
Actual value, decimal
In check mode, press [CHECK] to quit the check mode, and go into normal running
mode.
How to change the function switches?
No. Type State
of
switch
Function description
Connected Central
controller
J01
Changeover of Wired
controller and central
controller
Cut off
Wired controller
Connected
Set as simple controller
J02
Changeover of type of
wired controller
Cut off
Set as standard controller
Connected
Use the sensor in the wired
controller
J06
Selection of room temp.
sensor
Cut off
Use the sensor in the indoor unit
Connected Common
control
J07
Auto restart after power
failure
Cut off
Auto restart after power failure
Connected Yes
J03
Display of room
temperature
Cut off
No
ON
Set as slave controller
SW01
①
Changeover of master or
slave controller
OFF
Set as master controller
ON
℉
SW01
②
℃
or
℉
OFF
℃
Connected Indoor unit in shorted time
function
D1
Shorten time function
Cut off
Common control
Connected
Send compulsorily defrost signal
to indoor unit
D2
Compulsorily defrost
Cut off
Common control
Note: 1. The switches in grey can be operated after opening the cover of wired controller.
2. Switches or jumper wire must be adjusted when the wired controller is powered off. If the
wired controller is powered on, the above operations will be invalid.
3. Shorten time function
In normal operation, D1 is in short circuit, it will enter shorten time mode, and the time will be
shortened in the proportion of 60:1. In shorten time mode, LED will flash at the frequency of
0.5 second. Cut off D1, it will quit the shorten time mode and return to the normal operation
mode.
4. Compulsorily defrost
In heating mode 30
℃
and in High fan speed, D2 is in short circuit, it will enter compulsorily
defrost mode; cut off D2, it will quit. It is always be used when in testing to see if the defrost
function is good.
5. Lock function
-47-