3 OFF OFF ON OFF
4 OFF
OFF ON ON
5 OFF ON OFF OFF
6 OFF ON OFF ON
7 OFF ON ON OFF
8 OFF ON ON ON
9 ON OFF OFF OFF
10 ON OFF OFF ON
11 ON OFF ON OFF
12 ON OFF ON ON
13 ON ON OFF
OFF
14 ON ON OFF ON
15 ON ON ON OFF
16 ON ON ON ON
If you use central control type, SW1, SW2 will be used simultaneously.
Wiring request in central control type: port A-B is connected with indoor port CN16
(
A-B
)
through 2-core shield wire. Requirements:
1. Port A connects with port CN16
(
A
)
of all indoor units.
2. Port B connects with port CN16
(
B
)
of all indoor units.
Address on
central
controller
Indoor unit
address
SW2-3 SW2-2 SW2-1 SW1-4 SW1-3 SW1-2 SW1-1
1 1 OFF
OFF
OFF
OFF OFF OFF OFF
2 2 OFF
OFF
OFF
OFF OFF OFF ON
3 3 OFF
OFF
OFF
OFF OFF ON OFF
4
4
OFF OFF OFF OFF OFF ON ON
5
5
OFF OFF OFF OFF ON OFF OFF
6
6
OFF OFF OFF OFF ON OFF ON
7
7
OFF OFF OFF OFF ON ON OFF
8
8
OFF OFF OFF OFF ON ON ON
9 9 OFF
OFF
OFF
ON OFF OFF OFF
10
10
OFF OFF OFF ON OFF OFF ON
11
11
OFF OFF OFF ON OFF ON OFF
12
12
OFF OFF OFF ON OFF ON ON
13
13
OFF OFF OFF ON ON OFF OFF
14
14
OFF OFF OFF ON ON OFF ON
15
15
OFF OFF OFF ON ON ON OFF
16
16
OFF OFF OFF ON ON ON ON
17 17 OFF
OFF
ON
OFF OFF OFF OFF
18
18
OFF OFF ON OFF OFF OFF ON
19
19
OFF OFF ON OFF OFF ON OFF
20
20
OFF OFF ON OFF OFF ON ON
Commercial Air Conditioner
Model: AU182AFERA
AD182AMERA, AS182AVERA