135
Send oil return signal
oil return begins
oil return over
60s
ref. eliminated
30s
Oil return frequency
auto frequency
Low frequency
Inverter compressor
auto frequency
350pulse(E)
running indoor PMV
auto angle
auto angle
120pulse(E)
80(E)
stopped indoor PMV
OFF angle 5(E)
OFF angle 5(E)
Outdoor motor
AUTO
AUTO (TC or ambient temp. control)
AUTO
running indoor motor AUTO
AUTO (set fan speed)
AUTO
stopped indoor motor STOP
STOP
STOP
4-way valve
OFF
OFF
OFF
MULTI:
D: Entering condition
When the compressor running frequency is lower than 58Hz (E) continuously for 8 hrs, the system
will enter oil return operation. In the course of mode changeover, manual unit stop or protective
unit stop, the time will be accumulative. After the compressor restarts up, the time will be counted
continuously. In a continuous 8 hrs, if the compressor running frequency is not less than 72Hz for
over 10 minutes continuously, the accumulative time will be cleared. Also after the heating
defrosting, the time will be cleared.
E: Procedure
Cooling mode: refer to “the oil return procedure in cooling mode”
Heating mode: refer to “the oil return procedure in heating mode”
F: The protection treatment in oil return operation
In the course of oil return, because of protection or abnormal unit stop, after the unit restarts up,
the time will not be cleared, the system will need another oil return operation. In the refrigerant
flow course in the oil return of cooling mode or after the oil return, and within 5 minutes after the
refrigerant being eliminated is over, the anti-freezed protection is invalid, and also the low voltage
protection is invalid. But the other protection is valid.
In the course of oil return from heating mode to cooling mode, if abnormal condition occurs or the
unit stops for protection, then the system needs not another oil return within 3 minutes after the
unit stops and it will start up directly, then to heating mode.
In the course of oil return from heating mode to cooling mode, the anti-freezed protection is null
and void, and the low voltage protection is null either. The other protection is valid.
Oil return procedure in cooling mode:
Содержание AB25S2SC1FA
Страница 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Страница 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Страница 14: ...12 AB25S2SC1FA AB35S2SC1FA AD25S2SC1FA AD35S2SC1FA 420 370 892 850 185 640 90 760 152 2 Dimension unit mm...
Страница 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Страница 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Страница 25: ...23...
Страница 26: ...24...
Страница 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Страница 28: ...26...
Страница 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Страница 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Страница 31: ...29...
Страница 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Страница 33: ...31...
Страница 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Страница 39: ...37...
Страница 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Страница 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Страница 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Страница 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Страница 96: ...94 10 5 Air tightness test...
Страница 97: ...95 R32 R32 10 6 Vacuuming...
Страница 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...
Страница 182: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice...