9
Item Model
AD35S2SS1FA
Function
——
Cooling
Heating
capacity
W
3500
4000
sensible heat ratio
W
0.71
/
Dehumidifying capacity
10-³xm³/h
1.5
indoor unit
power supply
1PH, 220-240V~, 50/60Hz
Fan
Type × Number
——
centrifugal*2
Speed(H-M-L)
r/min
950/850/750/700
Fan motor output/input power
W
16/21
Air-flows (H/M/L)
m³/h
600/480/420/350
External static pressure
pa
0/10/20/30
Heat exchanger
Type / Diameter
mm
inner grooved pipe/
¢
7.0
Row
——
2
Total area
m²
0.11
Temp.scope
℃
2.0-7.0
Dimension
(LxWxH)
External
mmxmmxmm
850x420x185
Package
mmxmmxmm
1045x540x270
Drainage pipe (material,I.D/O.D)
mm
PVC 27/31
control type(Remote/Wired)
Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension
mm
none
Electricity Heater
kW
none
Noise level(H-
M-L)
Sound power level
dB(A)
53
Sound pressure level
dB(A)
35/32/29/26
weight(Net/Shipping)
kg/kg
16/21
panel
(
optional
)
panel model(color)
P1B-890IA/D
Dimension
External(L*W*H)
mmxmmxmm
890/190/100
(outlet panel)/
890/290.5/32.4
(inlet panel)
Package(L*W*H)
mmxmmxmm
938/335/220
Weight(Net/Shipping)
kg/kg
4/5
Piping
Refrigerant
Type
R32
Pipe
Liquid
mm
Φ6.35(1/4)
Gas
mm
Φ9.52(3/8)
Connecting method
Flared
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
Содержание AB25S2SC1FA
Страница 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Страница 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Страница 14: ...12 AB25S2SC1FA AB35S2SC1FA AD25S2SC1FA AD35S2SC1FA 420 370 892 850 185 640 90 760 152 2 Dimension unit mm...
Страница 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Страница 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Страница 25: ...23...
Страница 26: ...24...
Страница 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Страница 28: ...26...
Страница 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Страница 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Страница 31: ...29...
Страница 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Страница 33: ...31...
Страница 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Страница 39: ...37...
Страница 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Страница 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Страница 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Страница 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Страница 96: ...94 10 5 Air tightness test...
Страница 97: ...95 R32 R32 10 6 Vacuuming...
Страница 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...
Страница 182: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice...