127
the defrosting temp. sensor Te and outdoor ambient temp. sensor Tao, if they can meet the following condition,
entering in defrosting operation.
1. 5
o
C<(E)<Tao,Te<=-6
o
C<(E);
2. -6
o
C<(E)<=Tao<=5
o
C,Te≤C×Tao-α;
Herein :α=8(E) ;C:Tao<0
o
C;C=0.8; Tao≥0
o
C,C=0.6;
3.Tao<-6
o
C,Te≤-15
o
C<(E)and defrosting compressor run for 48 minutes in all.
Multi:
a. In heating mode, if the compressor has run for 10 minutes continously and run for 45 minutes in all, the
system will measure the defrosting temperature sensor Te and outdoor ambient temp. sensor TA, if the below
condition can be met for continous 5 minutes, the unit will enter defrosting operation:
Te≤C×TA-α
Herein: C: TA<0
o,
C=0.8 TA≥0
o
C, C=0.6
According to SW5-2, the setting is as follow: in the place easy to frost, it is H; when out of factory, it is M.
Jumper selection M (out of factory) H
α (
o
C)
8 (E)
6 (E)
b. Defrosting entering condition: -15
o
C≤C×TA-α≤-2
o
C;
c. Stop and Pause condition of compressor running accumulative time in heating mode:
Checking Stop: running operation changes from heating to cooling.
Checking Pause: thermostat OFF, or the unit stops.
Cancel condition:
It will take the max. 10 minutes from beginning defrosting to quit it. Te sensor will measure the condition of
outdoor heat exchanger, if the temp. is over 7
o
C for 60 seconds in all or is up to 12
o
C for 30 seconds in all, the
defrosting will be over.
2.3.6 Compulsory defrosting control
Enter condition: in heating mode, after receiving the compulsory defrosting signal from indoor unit, the unit will
perform the compulsory defrosting operation.
Cancel condition: Te≥12
o
C and keep for 1 minute or the defrosting time is over 10 minutes. The manual
defrosting signal of indoor unit will remain until the outdoor enters defrosting mode.
Note: When outdoor compressor not running, the unti still can enter manual defrosting, but it will comply with the
3-minute protection of compressor.
Содержание AB25S2SC1FA
Страница 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Страница 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Страница 14: ...12 AB25S2SC1FA AB35S2SC1FA AD25S2SC1FA AD35S2SC1FA 420 370 892 850 185 640 90 760 152 2 Dimension unit mm...
Страница 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Страница 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Страница 25: ...23...
Страница 26: ...24...
Страница 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Страница 28: ...26...
Страница 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Страница 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Страница 31: ...29...
Страница 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Страница 33: ...31...
Страница 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Страница 39: ...37...
Страница 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Страница 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Страница 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Страница 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Страница 96: ...94 10 5 Air tightness test...
Страница 97: ...95 R32 R32 10 6 Vacuuming...
Страница 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...
Страница 182: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice...