Service Diagnosis
46
NO
Remove fan motor after
switch off the power and
restart the unit, the LED
1 becomes light or flash.
Fan motor is
damaged. And
replace it with a new
one.
YES
NO
Test the fan motor terminal resistance
between pin 1(310V) and pin 4(0V), or
pin 5(15V) and pin 4(0V) of CN21 are
close to 0mΩ with a universal meter after
switch off the power.
NO
Remove the connection cable between
CN23 of outdoor PCB and CN10 of
module PCB. The LED1 becomes light
or flash.
The outdoor PCB is damaged.
Replace it with a new one.
YES
NO
The module PCB is damaged,
replace it with a new one.
YES
Содержание 1U50S2SJ2FA-1
Страница 11: ...Piping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV...
Страница 12: ...Operation range 5 Operation range 60 43 40 20 0 20 20 40 21 35 15 20 25 27 10 Domestic air conditioner...
Страница 31: ...Dimensional drawings 8 Dimensional drawings 9 Center of gravity 29 Domestic air conditioner...
Страница 56: ...Performance and curves diagrams 11 3 Cooling discharge pressure curves Domestic air conditioner 54...
Страница 57: ...Performance and curves diagrams 11 4 Cooling suction pressure curves 55 Domestic air conditioner...
Страница 58: ...Performance and curves diagrams 11 5 Heating capacity temperature curves 56 Domestic air conditioner...
Страница 60: ...Performance and curves diagrams 11 7 Heating discharge pressure curves 58 Domestic air conditioner...
Страница 61: ...Performance and curves diagrams 11 8 Heating suction pressure curves 59 Domestic air conditioner...
Страница 63: ...61 Do C omestic air ircuit Diagra conditioner ams r...
Страница 64: ...62 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram...
Страница 67: ...6 5 Domestic air conditioner Step Procedure Points Remove the fixting screws then lift the electrical box...
Страница 74: ...72 Domestic air conditioner Step Procedure Points Remove the fixing screw then lift the valve set...