Functions and control
17
Domestic air conditioner
When refrigerating, it is needed to satisfy
F-MIN-d(compressor’s Min_hz)< F<F-MAX-d(compressor’s Max_hz)
When heating, it is needed to satisfy
F-MIN-r (compressor’s Min_hz)< F<F-MAX-r (compressor’s Max_hz)
PID control :
The innital frequency Sn is determined by Pn . We can calculate Hzoutf according to the value of Kp ,Ki ,Kd,
Out_gain,Pn.Then , Fn = Sn + Hzoutf. The value of Fn is calculated in each sample time (60 seconds),and Fn is
adujusted according to previous frequency of Sn and filtered output of Hzoutf.
7.1.2 The outdoor fan control (Exchange fan)
When the fan is changed among every airflow speed (including stop blowing), in order to avoid the
airflow speed from skipping frequently, it must be kept under each mode for over 30 seconds, and then
it can be changed to another mode (when refrigerating, the time is changed to 15 seconds).
7.1.2.1 The outdoor fan control
Within three minutes of compressor starting, the compressor is controled according to the ambient temperature.
Tao
˄ć˅
Tao
<22
ć
22
ć
< Tao <28
ć
Tao
ı
29
ć
Refrigeration/dehumidification
(18K/24K)
2nd
level /2nd
level
3rd
level /4th
level 5th
level /6th
level
Tao
˄ć˅
Tao
<<10
ć
10
ć
< Tao <17
ć
Tao
ı
17
ć
Heating
5th level /6th
level
3th level /5th
level 3rd
level /2nd
level
After 3 minutes, the compressor is controled according to the ambient temperature and the frequency of the
compressor.
Refrigeration/dehumidification
frequency
˄
Hz
˅
18K
˄
24K)
<40 Hz
40 Hz-60 Hz
ı
60 Hz
Tao
˄ć˅
İ
22
2nd level
3rd level
5 th level(6 th)
22-28
3rd level
5 th level
7 th level(6 th)
ı
28
7 th level
Heating frequency
˄
Hz
˅
(18K/24K)
<51 Hz
51-70 Hz
ı
70 Hz
Tao
˄ć˅
İ
10
5nd level(3rd)
6rd level
7 th level
10-17
3rd level(2nd)
4 th level
5 th level(6 th)
ı
17
2nd level
7.1.3 The control of the outdoor Electronic expansion valve (EEV)
In cooling mode, the EEV opening range is 90~480 steps. The EEV opening is 90 steps when unit is
off.
In heating mode, the EEV opening range is 60~480 steps. The EEV opening is 60 steps when unit is
off.
After outdoor unit is off, the EEV opening keep the current on for 5 s, then open the EEV completely for
2 minutes, then become 90 steps (cooling) or 60 steps (heating).
Содержание 1U50S2SJ2FA-1
Страница 11: ...Piping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV...
Страница 12: ...Operation range 5 Operation range 60 43 40 20 0 20 20 40 21 35 15 20 25 27 10 Domestic air conditioner...
Страница 31: ...Dimensional drawings 8 Dimensional drawings 9 Center of gravity 29 Domestic air conditioner...
Страница 56: ...Performance and curves diagrams 11 3 Cooling discharge pressure curves Domestic air conditioner 54...
Страница 57: ...Performance and curves diagrams 11 4 Cooling suction pressure curves 55 Domestic air conditioner...
Страница 58: ...Performance and curves diagrams 11 5 Heating capacity temperature curves 56 Domestic air conditioner...
Страница 60: ...Performance and curves diagrams 11 7 Heating discharge pressure curves 58 Domestic air conditioner...
Страница 61: ...Performance and curves diagrams 11 8 Heating suction pressure curves 59 Domestic air conditioner...
Страница 63: ...61 Do C omestic air ircuit Diagra conditioner ams r...
Страница 64: ...62 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram...
Страница 67: ...6 5 Domestic air conditioner Step Procedure Points Remove the fixting screws then lift the electrical box...
Страница 74: ...72 Domestic air conditioner Step Procedure Points Remove the fixing screw then lift the valve set...