INSTALLATION
PAGE 23
ENGLISH
SE
C
TION D
Slim Duct Product Information
The Slim Duct Indoor Air Handler ships consisting of a single
assembly. The Slim Duct indoor unit is operated via a factory
supplied wired remote control.
that are located at all four corners of the Slim Duct assembly..
The Slim Duct unit receives 230 volt line voltage from a
connection at the outdoor condensing unit. There is no
requirement for independent line voltage connections.
The Slim Duct unit has a built-in condensate pump and
Duct unit. This hose connects the Slim Duct condensate
drain outlet to the building’s condensate drain s ystem.
Included with the Slim Duct unit is factory pr ovided insulating
tape. This tape should be placed voer the refrigerant piping
connections at the indoor unit to prevent sweating.
Built-in
Condensate
Pump and
Float Switch
Section D - Indoor Unit Installation - Slim Duct
Indoor
AD07SL2VH*
AD09SL2VH*
AD12SL2VH*
AD18SL2VH*
Rated Cooling Capacity Btu/hr
7,000
9,000
12,000
18,000
Rated Heating Capacity Btu/hr
8,000
10,000
13,000
19,000
Voltage, Cycle, Phase V/Hz/-
208-230/60/1
208-230/60/1
208-230/60/1
208-230/60/1
Fan Speed Stages
5+Auto
5+Auto
5+Auto
5+Auto
Quiet) CFM
353/312/270/230/188
353/312/270/230/188
400/353/282/247/218
540/500/447/365/306
Motor Speed (Turbo/High/Med/Low/
Quiet) RPM
950/850/750/650/550
950/850/750/650/550
1050/950/800/700/600
1050/950/850/750/650
Max. External Static Pressure in.W.G
(Pa)
0.16 (40)
0.16 (40)
0.16 (40)
0.16 (40)
Indoor Sound Le vel dB ( Turbo/High/
Med/Low/Quiet)
35/33/29/26/21
35/33/29/26/22
38/35/29/26/23
31/29/23/29/25
Dimension: Height in (mm)
7 5/16 (185)
7 5/16 (185)
7 5/16 (185)
7 5/16 (185)
Dimension: Width in (mm)
33 7/16 (850)
33 7/16 (850)
33 7/16 (850)
46 1/16 (1170)
Dimension: Depth in (mm)
16 9/16 (420)
16 9/16 (420)
16 9/16 (420)
16 9/16 (420)
Weight (Ship/Net)- lbs (kg)
47.2/36.8 (21.4/16.7)
47.2/36.8 (21.4/16.7)
47.2/36.8 (21.4/16.7)
61.8/48.5(28/22)
Connections
Flare
Flare
Flare
Flare
Liquid O.D. in
1/4
1/4
1/4
1/4
Suction O.D. in
3/8
3/8
3/8
1/2
Drainpipe Size O.D. in
1 1/4
1 1/4
1 1/4
1 1/4
Internal Condensate Pump
Standard
Standard
Standard
Standard
Max. Drain-Lift height in(mm)
27 9/16 (700)
27 9/16 (700)
27 9/16 (700)
27 9/16 (700)
Introduction - Overview
YR-E17 Wired Controller
See Section E for more information
Содержание 1U12LC2VHA
Страница 6: ... This page intentionally left blank ...
Страница 12: ... This page intentionally left blank ...
Страница 16: ... This page intentionally left blank ...
Страница 36: ... This page intentionally left blank ...
Страница 41: ... This page intentionally left blank ...