hager witty park XEV6 Series Скачать руководство пользователя страница 7

6LE002957D

6LE002957D

Not used = 0

D/N Behaviour

D/N = 1 

Starts / Stops charging

Load shedding mimi = 2 

Load shedding at Night

Load shedding 0 A = 3 

Load shedding at Night

D/N input never used 

No parameters to set

D/N Delay (0..1440)

D/N Activation mode

D/N Behaviour

D/N Activation mode

D/N Activation mode

Exclusive 

Start charging at Night 

Stops charging during the day

230 V = Day 

0 V = Night

0 V = Day 

230 V = Night

230 V = Day 

0 V = Night

0 V = Day 

230 V = Night

Inclusive 

Starts charging at Night

230 V = Day 

0 V = Night

0 V = Day 

230 V = Night

c.6 Advanced functions
• Tethered cable:

 The charging station will adapt its behaviour as it has a tethered cable.

• Charge delay after blackout:

 defines delay before a charge restarts after a blackout (1 to 600 seconds). If 0, random delay between 5-120 seconds.

• Indoor/outdoor:

 If outdoor is set, the charging station will ignore the EV ventilation request. If indoor is set, the charging station will stop the charge if the  

 

 

EV request ventilation.

• EV41: 

Setting that allow to start a charging session below 7A in single phase and 13A in three phases.

 

 

If the setting is EV41 is disabled = 0 (Default value):

 

 

mini current for one / three phase = 6A 

 

 

Calculate the reactive current 

 

 

In case reactive current > 2.5A (EV41 requirement), the charge stop 

  

StatusNotification with OCPP status = SuspendedEVSE to indicate that the current is too low and MUST be increase.

 

 

If the setting Zoe_ph1 = 1 is set:

 

 

mini current for one phase = 7A 

 

 

mini current for three phase = 13A

 

 

If the setting Zoe_ph2_kangoo_twingo = 2 is set : 

 

 

mini current for one phase = 6A 

 

 

mini current for three phase = 7A

c.7 Sub-metering

Two MID meters are integrated in the charging station. They are communicating through modbus RTU with the communication board. Address 1 is set two 
the left side meter and address 2 is set for the right side meter.

12

13

7. HMI

Status

Colour

Station is ready

Green

Charging

Green breathing

Charging management - lowering the power during a session 
Charging management - External signal - temporary charge stop (D/N INPUT)
Extended charging (interrupted charging, lowered power, etc.)
Charging management - load shedding during a session 
Fault - Power failure

Off

Reservation

Solid purple

Fault - Defective cable - coding resistance absent or out of normative tolerance

Fix red

Fault - Defective communication between station and EV - Short circuit between CP and PE (CP = 0V - State E)
Fault - 4x EV over-consumption - The EV charges at too high current (4x in the same charging session)
Fault - Ventilation required - The EV requires a ventilation of the charging room
Fault - Defective communication between station and EV - diode error (connection to something other than an EV)
Fault - Invalid badge

Red/white 3 time then green fix

Fault - Charging rate on 6A in single-phase

Fix red

Fault - Charging rate on 10A in three-phase
Fault - Charging rate on 6A in three-phase
Locking of the awaiting charging authorisation

Cycle blinking green / empty

Awaiting charging authorisation
Awaiting cable disconnection

Blinking green / empty

Pause EV charging

Blinking  0,25s green / 0,75s empty

Содержание witty park XEV6 Series

Страница 1: ...e installed only by a professional electrician fitter according to local applicable installation standards Conform to SELV installation rules 2 General description Strip light RFID Card Reader Socket...

Страница 2: ...ing space at the rear Contact detection fixed on the contactor Controller MID energy meter version specific Grommet plate Controller power supply Terminal blocks Plug N 3 M3T2S socket lockable Plug N...

Страница 3: ...nal Installation Area 713 1472 765 480 1239 330 1089 2 0 2 2 0 2 1 7 5 355 355 1300 max 233 87 50 1395 max 435 235 8 5 54 4x not included 2x 2x 175 110 325 650 325 70 350 250 190 250 500 250 Foundatio...

Страница 4: ...coder wheel to an authorised threshold Then turn on the terminal a steady green light should light up N Three phase power supply 1 X1 X2 Controller power supply MZ203 Trigger circuit connection X3 Thr...

Страница 5: ...onnection c Protections Single phase Electrical cabinet Station Protection integrated in the electronic board Power 4 kVA only MZ203 transmitter coils Fault detected Information via solid red indicato...

Страница 6: ...e management is done through the local configurator 10 11 c 2 OCPP configuration Enables configuration of the connection to an OCPP server to be retrieve from the CPO OCPP server OCPP server address A...

Страница 7: ...hase 7A mini current for three phase 13A If the setting Zoe_ph2_kangoo_twingo 2 is set mini current for one phase 6A mini current for three phase 7A c 7 Sub metering Two MID meters are integrated in t...

Страница 8: ...power load 7kW 1 phase Version 22kW 3 phases Version Class of electrical protection Class 1 Socket outlet Mode 3 T2S Domestic socket Mode 2 Overvoltage category III Mechanical characteristics Weight 3...

Страница 9: ...socket and the EV plug should only be used if they have been specifically designed and approved by the vehicle manufacturer or the manufacturer of the EV power system and meet national requirements T...

Отзывы: