6. Charging station software configuration
Before using the configuration software, please refer to the charging station installation manual. Device to be installed and configured only by an electrical
installer according to the installation standards applicable in the country.
The charging station is equipped with a web configurator to configure it. By default, the charging station is configured as a “DHCP client” and, as a result,
requires a router with a “DHCP Server” function to operate within the LAN.
If the charging station does not detect the DHCP server, it automatically assigns a fixed IP address (by default: 192.168.0.101), which can be set in the
software configuration.
a. Web server access
There are several ways to access the charging station configurator. The configurator is compatible with different screen sizes, such as a laptop, tablet or
smartphone.
a.1 Via the charging station name (HostName)
The web server can be accessed directly by entering the address of the charging station name (Host name) in the web browser. The exact address is specific
to each charging station, indicating the last 6 characters of its UID code specified on the communication board in the charging station.
Address format: https://hager-evcs-[6Last_caracters_UID.local]/ (example: https://hager-evcs-ab4df5.local/). Except android version<12 (preferred way using
IP address)
a.2 Via its IP address
The web server can be accessed by entering the charging station’s IP address in the web browser. The charging station’s IP address can be detected using
an “IP Scanner” third-party application or if the charging station does not detect the DHCP server using its fallback IP address after 120 seconds (default:
https://192.168.0.101)
You can restore the default ip configuration with the below procedure:
• Switch off the charging station
• put the rotary wheel on 9
• switch on the charging station
• wait 30 sec
• put off the charging station
• put the rotary wheel on the chosen value
• switch on again the charging station
The charging station could be set in DHCP server mode with the procedure below:
• Switch off the charging station
• put the rotary wheel on 8
• switch on the charging station
• wait 30 sec
• put off the charging station
• put the rotary wheel on the chosen value
• switch on again the charging station
b. Identification page
The configurator is protected by a user name and password. By default, these credentials are:
User name: admin
Password: #HagerXEV60x
When connecting for the first time, you will be asked to change the password to a “strong” password.
You can change the password in the configurator. If you lose these credentials, you can reset them to the default value with the below procedure:
• Switch off the charging station
• put the rotary wheel on 9
• switch on the charging station
• wait 30 sec
• put off the charging station
• put the rotary wheel on the chosen value
• switch on again the charging station
c.1 Standalone mode
When the charging station is configured with the “
Standalone
” setting, the charging station will run without OCPP communication.
The badge management is done through the local configurator.
10
11
c.2 OCPP configuration
Enables configuration of the connection to an OCPP server (to be retrieve from the CPO).
•
OCPP server:
OCPP server address
•
Authentication:
authentication method for the OCPP server
•
Login:
OCPP user name
•
Password:
OCPP password
•
ChargePoint ID:
charging station user name (minimum 1 character, by default : serial number of the charging station)
c.3 OCPP mode
4 different mode are available :
• Full OCPP (by default):
the CPO will get all the charging sessions data and will do the RFID cards management
• Free access OCPP:
the CPO will get all the charging sessions data but the RFID cards aren’t required in order to start a charging session.
• Standalone Park:
The charging station isn’t supervised by a CPO and will manage the RFID cards via the “Whitelist”.
The Whitelist can be completed manually by entering the RFID badge credentials, imported via a .txt file, or learned by enabling the
“Add by scan” mode and swiping the badges on the charging station’s RFID reader.
• Standalone Home:
The charging station isn’t supervised by a CPO and will be in free access.
c.4 Network
Enables configuration of the network
• DHCP client:
(by default) connects to a DHCP server or assigns a fixed IP (if no DHCP server, fallback IP address will be active after 120 seconds)
• IP address:
defines the fixed IP
• Fallback IP address:
defines the IP if there is a DHCP error
c.5 Physical installation
Enables the charging station configuration to be completed.
• Phase rotation:
enables the metering information to be fed back per phase on the correct phase, should the charging station not be supplied in the
standard sequence of phases (default value : L1-L2-L3).
• CHP:
Physical input 24 VDC which allow to do load shedding.
-
If the setting is at 0 (default value), the activation of the input will reduce the charging session to the minimum (depending of the EV41 setting).
-
If the setting is at 1, the activation of the input will stop the charging session.
• D/N behaviour:
Physical 230V input which allow.
-
If the setting is at 0 (default value), the charging station will start to charge immediately.
-
If the setting is at 1, the charging station will authorize the charge when the “D/N activation mode” will be at “night”.
-
If the setting is at 2, the charging station will reduce the charging session to the minimum (depending of the EV41 setting) when the “D/N
activation mode” will be at “night”.
-
If the setting is at 3, the charging station will suspend the charging session when the “D/N activation mode” will be at “night”.
• D/N activation mode:
-
If the setting is at 0 (default value)-> 230V = Night / 0V = Day
-
If the setting is at 1 -> 0V = Night / 230V = Day
• D/N activation delay:
time after when the “night” value will be taken in account (only if day/night setting is activated).
From 0…1440 min (Default value = 0)
• D/N inclusive and exclusive:
this setting is only available if the parameter “D/N behaviour” is at 1.
Inclusive = 0 (Default value)
The charge is authorized when transition Day -> Night (Depends on D/N activation mode).
Once authorized, the charge will continue until the car is unplug.
Exclusive = 1
The charge is authorized when transition Day -> Night (Depends on D/N activation mode).
The charge is deauthorized when the input goes from Night -> Day (Depends on D/N activation mode).