5. Electrical installation

a.  Power supply

Power terminal block (230V/32A) for rigid cable of max. 10 mm².
Control terminal blocks of transmitter coils for rigid cable of max. 1.5 mm².
Power supply terminal block (230V) of the controller for rigid cable of max. 

1.5 mm².
Upstream protection for controller power supply: Circuit breaker 16A, C 

curve 

b.  Maximum power load

The maximum power load is determined using the encoder wheel that can 

be turned to the desired amperage.
If the LED indicator light is a solid red, turn off the power, wait for 15 

seconds and then change the position of the encoder wheel to an 

authorised threshold. 
Then, turn on the terminal: a steady green light should light up.

N

Three-phase power

supply 1

(-X1/-X2)

Controller power

supply

MZ203 Trigger circuit

connection

(-X3)

Three-phase power

supply 2

(-X3/-X4)

L1 L2 L3

N L1 L2 L3

N LST

N LST

-X0.1

-X0

-X0.3

-X3/4

MZ203 trigger circuit

connection

(-X1)

N

L

Wiring diagram (version-specific)

Maximum 

charging 

rate

3-phases station

1-phase station

6 A

Not authorised by ZE Ready 

1.2

Not authorised by ZE Ready 

1.2

10 A
13 A
16 A
20 A
25 A
32 A
40 A

Prohibited for the electrical safety of the terminals

50 A
63 A

y

o

PIN

➞➞

The terminal MUST be mounted 

on its base  BEFORE if used 

 

attaching the vector cabinet.

 

The equipotential bonding   

 

must be established between  

 

the terminal, foot and base.

O

6

7

* Earthing point to connect to 

the earth system

*

Содержание witty park XEV6 Series

Страница 1: ...e installed only by a professional electrician fitter according to local applicable installation standards Conform to SELV installation rules 2 General description Strip light RFID Card Reader Socket...

Страница 2: ...ing space at the rear Contact detection fixed on the contactor Controller MID energy meter version specific Grommet plate Controller power supply Terminal blocks Plug N 3 M3T2S socket lockable Plug N...

Страница 3: ...nal Installation Area 713 1472 765 480 1239 330 1089 2 0 2 2 0 2 1 7 5 355 355 1300 max 233 87 50 1395 max 435 235 8 5 54 4x not included 2x 2x 175 110 325 650 325 70 350 250 190 250 500 250 Foundatio...

Страница 4: ...coder wheel to an authorised threshold Then turn on the terminal a steady green light should light up N Three phase power supply 1 X1 X2 Controller power supply MZ203 Trigger circuit connection X3 Thr...

Страница 5: ...onnection c Protections Single phase Electrical cabinet Station Protection integrated in the electronic board Power 4 kVA only MZ203 transmitter coils Fault detected Information via solid red indicato...

Страница 6: ...e management is done through the local configurator 10 11 c 2 OCPP configuration Enables configuration of the connection to an OCPP server to be retrieve from the CPO OCPP server OCPP server address A...

Страница 7: ...hase 7A mini current for three phase 13A If the setting Zoe_ph2_kangoo_twingo 2 is set mini current for one phase 6A mini current for three phase 7A c 7 Sub metering Two MID meters are integrated in t...

Страница 8: ...power load 7kW 1 phase Version 22kW 3 phases Version Class of electrical protection Class 1 Socket outlet Mode 3 T2S Domestic socket Mode 2 Overvoltage category III Mechanical characteristics Weight 3...

Страница 9: ...socket and the EV plug should only be used if they have been specifically designed and approved by the vehicle manufacturer or the manufacturer of the EV power system and meet national requirements T...

Отзывы: