5. Electrical installation
a. Power supply
Power terminal block (230V/32A) for rigid cable of max. 10 mm².
Control terminal blocks of transmitter coils for rigid cable of max. 1.5 mm².
Power supply terminal block (230V) of the controller for rigid cable of max.
1.5 mm².
Upstream protection for controller power supply: Circuit breaker 16A, C
curve
b. Maximum power load
The maximum power load is determined using the encoder wheel that can
be turned to the desired amperage.
If the LED indicator light is a solid red, turn off the power, wait for 15
seconds and then change the position of the encoder wheel to an
authorised threshold.
Then, turn on the terminal: a steady green light should light up.
N
Three-phase power
supply 1
(-X1/-X2)
Controller power
supply
MZ203 Trigger circuit
connection
(-X3)
Three-phase power
supply 2
(-X3/-X4)
L1 L2 L3
N L1 L2 L3
N LST
N LST
-X0.1
-X0
-X0.3
-X3/4
MZ203 trigger circuit
connection
(-X1)
N
L
Wiring diagram (version-specific)
Maximum
charging
rate
3-phases station
1-phase station
6 A
Not authorised by ZE Ready
1.2
Not authorised by ZE Ready
1.2
10 A
13 A
16 A
20 A
25 A
32 A
40 A
Prohibited for the electrical safety of the terminals
50 A
63 A
y
o
PIN
➞
➞➞
➞
The terminal MUST be mounted
on its base BEFORE if used
attaching the vector cabinet.
The equipotential bonding
must be established between
the terminal, foot and base.
O
6
7
* Earthing point to connect to
the earth system
*