Connections
Power circuits
Standard Connection priority source on switch I
The product is delivered from the factory with the following configuration:
• the source 1 on control module (connectors 101 to 106) is linked to switch I
• the source 2 on the control module (connectors 201 to 206) is linked to switch II.21
Load
Source
2
Source
1
1
2
Connections
Take into account connection cables length for section selection.
125 A 160 A 250 A 400 A 630 A
800 A
1000 A 1250 A 1600 A 2000 A
2500 A
3200 A
Minimum cables section
Cu (mm
2
) at Ith
35
50
95
185
2 x 150 2 x 185 -
-
-
-
-
-
Minimum bars section
Cu (mm
2
) at Ith
-
-
-
-
2x30x5 2x40x5 2x60x5 2x60x5 2x80x5 2x100x10 2x100x10 2x100x10
Maximum cables section
Cu (mm
2
)
50
95
150
240
2 x 300 2 x 300 4 x 185 4 x 185 6 x 185 -
-
-
Maximum bars width Cu
(mm) at Ith
20
20
32
32
50
63
63
63
100
100
100
100s
00
0
Recommended tightning
Maximum tightning
torque
torque
M6: 4,5 N.m
M6: 5,4 N.m
M8: 8,3 N.m
M8: 13 N.m
M10: 20 N.m
M10: 26 N.m
M12: 40 N.m
M12: 45 N.m