41
Installation
Terminal Shrouds (available from 125 to 630 A)
• Upstream, downstream, front or back mounting
• Only possible to mount front terminal shroud in case of
bridging bars.
Protection Screens
Customer mounted accessories
Bridging Bars
125 - 630A
Recommended tightning
Maximum tightning
torque
torque
M6: 4,5 N.m
M6: 5,4 N.m
M8: 8,3 N.m
M8: 13 N.m
M10: 20 N.m
M10: 26 N.m
M12: 40 N.m
M12: 45 N.m
Possible to mount the bridging bars on either side of the
switch.