![hager HIC4 Series Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/hager/hic4-series/hic4-series_operating-instructions-manual_3275275056.webp)
54
LCD
Denomination/Definition
Setting range
Default value
Network 1 over voltage threshold
from 102 to120%
115 %
Network 1 over voltage threshold
hysteresis
from 101 to119% (<oU)
110 %
Network 1 under voltage threshold
from 80 to 98%
85 %
Network 1 under voltage threshold
hysteresis
from 81 to 99%(>uO)
95 %
Network 2 over voltage threshold
from 102 to120%
115 %
Network 2 over voltage threshold
hysteresis
from 101 to119% (<oU)
110 %
Network 2 under voltage threshold
from 80 to 98%
95 %
Network 2 under voltage threshold
hysteresis
from 81 to 99%(>uU)
85 %
W
$YDLODEOHVRXUFH
&RQWUROOHGYDOXHYROWDJHV
2YHUYROWDJHWKUHVKROGR8
8QGHUYROWDJHWKUHVKROGX8
2YHUYROWDJHK\VWHUHV\V
WKUHVKROGR8K
8QGHUYROWDJHK\VWHUHV\V
WKUHVKROGX8K
q
Values definition: % of nominal values Hysteresis values range is limited by thresholds values.
Programming :
Volt Menu :
Threshold detection starts from the loss of source or source return sequence
Operation
Содержание HIC4 Series
Страница 35: ...33...
Страница 69: ...67...
Страница 70: ......
Страница 71: ......
Страница 72: ...6H5110_00 Hager 01 2014 OCOM 119337...