6. Programming the product

The product is programmed after wiring 

verifi cation  tests  through  the  front  of  the 

product Controller in 5 steps:

Note

Ensure that the product is in “Manual Mode”, 

powered and  with at least one network 

supply available.

SET the 4 Dip Switches using a small screw 

driver. Possible variants vary from positions 

“A to H” as described in the table below. For 

convenience, the position functions are also 

described on the front of the ATS controller 

adjacent to the dip switches.

Note

The  READY  LED  will  fl ash  green  as  soon  as 

settings are changed and until the new settings 

have been saved by pressing the PROG OK 

button momentarily (refer to Step   ).

Dip Switch Setting Options

Dip switch 1

A/B

A Three Phase Network 

B Single Phase Network  

(Attn: Dipswitch 2 is inactive in this position)

Dip switch 2

C/D

C Three Phase 4 wire Network (Including Neutral)  

(Allows to detect a loss of neutral for unbalanced loads)

D Three Phase 3 wire Network (Without Neutral)

Dip switch 3 

E/F

E Without a time delay in Zero Position (DBT = 0 sec) 
F Zero position time delay set to 2s (DBT = 2 sec) 

Dip switch 4 

G/H

G Main - Generator Application 
H Main - Main Application

1

Dip switch setting options

2

Potentiometer setting options

SET the 4 potentiometers  using a small screw  

driver paying attention to the arrow indicating 

the position. There are a total of 14 positions 

for which the specifi c settings are described in 

the table below.

Note

The  READY  LED  will  fl ash  green  as  soon  as 

settings are changed and until the new settings 

have been saved by pressing the PROG OK 

button momentarily (refer to Step   ).

Functional description

Pot. 1

Un

Pos N° 0 = Auto Con.guration position 

Pos N° 1 to 13 = Preset Volt and Hz Config.

Pot. 2

ΔU ΔF

Delta U: Adjustable from 5 to 20%

Delta F: Adjustable from 3 to 10%

Pot. 3

FT

Supply Source Failure Time: 0 to 60s

Pot. 4

RT

Supply Source Return Time: 0 to 60 min

Position Setting Identifi cation

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Pot 1

Un PhPh /

PhN

Auto

Conf

220 /

127V

380 /

220V

400 /

230V

415 /

240V

480 /

277V

208 /

120V

220 /

127V

230 /

132V

240 /

138V

380 /

220V

400 /

230V

415 /

240V

480 /

277V

-

Fréq.

50Hz

60Hz

Pot 2

Seuil U/F en %

 de Un / Fn

-

5 /

3%

6 /

3%

7/

4%

8 /

4%

9 /

5%

10 /

5%

11 /

6%

12 /

6%

13 /

7%

14 /

7%

15 /

8%

16 /

8%

18 /

9%

20 /

10%

Pot 3 FT (s)

0

1

2

3

4

5

8

10

15

20

30

40

50

60

-

Pot 4 RT (min)

0

1

2

3

4

5

8

10

15

20

30

40

50

60

-

Whatever Pot 1 trimming , it is IMPERATIVE to set Pots 2 to 4.

Set dip

1

Press   

>2s

3

Press 

<60ms

4

Set pot

2

Ready

5