background image

5. Check

In manual mode, 

check the wiring.

If OK power up

the product

LED Green = 

“Power” : ON
LED Red =

“Manuel/Defaut”: ON

3

6LE001152A.f

1  Preferred source       2  Alternate source

&

 Position 0 order

é

 

 

Position 1 order

"

 Position 2 order

'

 Zero position priority order

(

 Remote Control Enable (Priority over Auto)

§

 Product Available output (Motor)

è

 Position II aux contact

!

 Position I aux contact

ç

 Position 0 aux contact

a

 O/P to HZI910 remote display

z

 Product available output (ATS)

e

 I/P Inhibition of the ATS controls

r

 I/P Manual retransfer

t

  S2 Stability Time Bypass: 2AT

y

  Priority to TEST ON LOAD: TON

u

  TEST OFF LOAD Signal: TOF

i

  TEST ON LOAD Signal: TON

o

  Not used

p

  Contact “Start/Stop Genset”: if S1

is not available the NC contact le 

contact (71-72) is close

q

  Contact “Start/Stop Genset”: if S1

is not available the NO contact le

contact (71-74) is open

s

  Voltage Sensing Inputs

d

  Power Supply Inputs

Example: control wiring for a 400VAC application having a 3 phase and neutral supply

4. Power supply, sensing and control wiring

Use cables with 1,5 to 2,5 mm

2

 section.

Screw M3

Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm

Recommanded to use

the voltage sensing kit

ATS Power Supply input II

Power Supply II - L

Power Supply II - N

208-277 VAC ±20%:

50/60 Hz

ATS Voltage Sensing input

Source supply II

S II - Phase 1
S II - Phase 2
S II - Phase 3

600 VAC (ph-ph) max

S II - Neutral

332 VAC (ph-n) max

 ATS Module Control Inputs

 

(Fixed)

Contact 

Genset Start/Stop 

(Product available)

Signal

ATS Power Supply input I

Power Supply II - L
Power Supply II - N
208-277 VAC ±20%:
50/60 Hz

ATS Voltage Sensing input

Source supply II

S I - Phase 1

S I - Phase 2

S I - Phase 3

600 VAC (ph-ph) max

S I - Neutral

332 VAC (ph-n) max

ATS Module Control Inputs

 

(Fixed)

ATS Module Output Contact

(Product available)

Remote interface

RJ45 - to HZI910

2

10

4103

312 313 314 315 316 317 63A64A 24 14 04 13

RJ

10

2101

10

5

10

6

41

4413

41

5

41

6

41

7

64

B63B

72

20

1

71

202

20

5206

20

4

20

3

21

0

20

9

20

8

20

7

74

1

F1

F2

L1

L2

L3

N

L1

L2

L3

N

HZI910

Отзывы: