6

6LE001152A.f

&

  MANUAL Mode LED indication.

(yellow steady light when in Maual Mode).

é

  AUTO Mode LED indication

(green steady light when in Auto mode 

with no timers running, green fl ashing light 

when in Auto with timers running in the 

background).

"

  REMOTE CONTROL Mode LED indication. 

Yellow steady light when in remote control 

mode.

Remote control mode is achieved with the 

Auto/Manu selector switched to Auto and 

terminals 312 closed with terminal 317. 

Remote control orders are received through 

closing 314 to 316 with 317.

'  

TEST ON LOAD CONTROL Mode LED 

indication (yellow steady light when in TON 

mode)

(

  TEST OFF LOAD CONTROL Mode LED 

indication (yellow steady light when in TOF 

mode).

§ 

 Switch 1 LED position indication.

(green when in position 1).

è

  Source supply I availability LED indication

(green when supply I voltage is within the 

set limits).

!

  Zero position LED indication

(yellow when in position 0).

ç

  Switch 2 LED position indication.

(green when in position 2) 

a  

Source supply II availability LED indication 

(green when supply II voltage is within the 

set limits).

z

  Sealing screw location 1 for use with 

sealing  cover (available as an accessory

e

  Potentiometer 1: Network Confi guration. 

(Auto Confi guration 

or 

refer to the confi guration guide sticker on 

the front of the product when using the 

predefi ned setting positions 1 to 13).

r

  Potentiometer 2 : Voltage and Frequency 

threshold settings. (Refer to the 

confi guration guide sticker on the front of 

the product to set the V / Hz threshold. 

Positions 1 to 14).

t

  Potentiometer 3: Supply FAILURE Time (FT) 

Adjustable from 0 to 60 seconds

y

  Potentiometer 4: Supply RETURN Time (RT) 

Adjustable from 0 to 60 minutes.

u

  READY LED indication (green steady light: 

product in AUTO, Watchdog OK, Product 

Available to changeover; green fl ashing: 

settings displayed not saved or have been 

changed since last saved. Press PROG OK 

button in manual mode to save or revert to 

last saved settings).

i

  Sealing screw location 2 for use with the 

sealing cover.

o

  FAULT LED indication (red steady light in 

case of an ATS controller internal fault).

p

  Confi guration dip switches: 

(4 dip switches with 2 positions in each A 

to H).

q

  PROG OK: confi guration save push button 

(ATTN: active in Manual Mode ONLY). 

Press briefl y to confi rm and save all set 

confi guration settings.

Hold pressed for 2 seconds to set the 

network supply voltage and frequency by 

Auto Confi guration.

This is to be followed by pressing briefl y to 

save the set value confi gured.

s

  Green LED Indication: power

d

  Red LED Indication: Product Unavailable / 

Manual Mode / Fault Condition

f

  Auto / Manual mode selector switch (Kky 

version available as an option)

g

  Padlocking facility (up to 3 padlocks of dia. 

4 – 8mm)

h

  Emergency manual operation shaft location 

(accessible only in manual mode)

j

  Switch position indication window: 

I (On switch I) 

O (Off) 

II (On switch II.)

7A. Automatic operation

Ensure that the 

emergency handle 

is not inserted in the 

product and turn 

the mode selector 

to the AUT position.

LED green = “Power” : 

ON
LED  Manuel/Default : 

OFF

LED green "AUT": ON

7B.  Automatic operation: 

remote control

   Impulse 60 ms

   Impulse 

maintened

To enable control, 

close contact 312 with 

317.

For contactor logic 

bridge contact 316 

with 317.
To operate: close the 

contact corresponding 

to the desired position.
To force the product to 0 position “OFF” bridge 

contact 313 with 317.

7C. Manual operation

90°

90°

I

II

0

7D.  Padlocking mode

(Standard: in position O) 

Foreseen for max. 3 padlocks Ø 4-8mm

Impulse logic 

Contactor logic

Order I

Order O

Order II

Position I

Position O

Position II

AUT

AUT

f

g

h

j