Esento-RDU Installation, Commissioning & Operating Manual
Approved Document Ref: DOC00636 Issue 4.0
9
SETUP & PROGRAMMING
2
1
2
3
Panel Wide Settings
There are 11 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 11 programmable
options are represented by fire zone LEDs 1 - 11, Option 2 being the, ‘set
number of repeater panels’ setting.
Use button 1 to move to option 2
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Fire LED Programming Option
1
2
Set number of repeater panels on system
3
4
5
6
OPTION 2.
Set Number of Repeater Panels on System
With the zone 2 fire LED lit, the amber, fault LEDs will show the current quantity of repeaters set 0 - 8.
(1 LED lit = 1 repeater, 2 = 2 etc..).
Press the ENTER button, zone 2 fire LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the quantity. Button 1 increases, button 3 decreases.
When finished press the ENTER button again and the zone 2 fire LED will return to steady ‘view mode’.
Press button 1 for 3 seconds to exit programming mode 2-1-2-3.
To set the number of repeater panels at the main control panel use: