Esento-RDU Installation, Commissioning & Operating Manual
Approved Document Ref: DOC00636 Issue 4.0
8
SETUP & PROGRAMMING
REPEATER PANEL SETUP & PROGRAMMING
Up to 8 repeater panels can be supported on a system. The remote display units are fully functional with
‘Silence’ ‘Resound’ and ‘Reset’ controls, as well as Disable and Test Mode functions. It is possible to
disable the controls of each or all repeater panels to make them passive.
Repeater Comms PCB
To run remote display units, a Comms PCB (TPCA05) must be fitted to the main control panel.
The Comms PCB fits into the control panel on top of the main circuit board where the ribbon cable from
the display board is normally plugged.
To fit the Comms PCB, power down the panel, un-plug the display board ribbon cable from the main circuit
board and plug the Comms PCB into the socket instead.
A socket is provided on the top of the Comms PCB to re-connect the display board ribbon cable.
In order to initialise the Comms PCB in the main control panel the Network/Repeater mode DIL switch,
located on the main circuit board, must be switched to the ON position. For the 16-32 zone size panel this
is switch No. 3. For the 2-12 zone size panels this is switch No. 7. If this has not been set correctly the
‘System Fault’ lamp will be illuminated.
See panel manual for further details of fitting a TPCA05, Comms PCB.
Set Number of Repeater Panels
The control panel will need to be programmed for the number of repeater panels on the system. See over
page.
The number of repeater panels on the system is programmed at the main control panel with
Level 3 programming mode active
(see panel manual for details of Level 3 programming
mode).
Addressing
Each remote display unit needs to have a seperate address. The addressing is done using the 4 DIL
switches located on the circuit board (labelled SET ADDRESS) using binary code values, see diagram
below.
The address should be set in sequence from 1 - 8, first display unit = address 01, next unit = address 02
etc. The main control panel should always be address 00 (all switches off).
1
2
3
4
ON
ADD 01
1
2
3
4
ON
ADD 02
1
2
3
4
ON
ADD 03
1
2
3
4
ON
ADD 04
1
2
3
4
ON
ADD 05
1
2
3
4
ON
ADD 06
1
2
3
4
ON
ADD 07
1
2
3
4
ON
ADD 08