Installation, Commissioning & 

Operating Manual

MARINE APPROVED 2 - 4 ZONE CONVENTIONAL 

CONTROL PANEL

Approved Document UI-ESEN4MAR-01 Issue  6.0

MED Ref: 0832/15

Содержание ESEN-2MAR

Страница 1: ...Installation Commissioning Operating Manual MARINE APPROVED 2 4 ZONE CONVENTIONAL CONTROL PANEL Approved Document UI ESEN4MAR 01 Issue 6 0 MED Ref 0832 15 ...

Страница 2: ... No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manufacturer s policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice E O E IMPORTANT SAFETY NOTE...

Страница 3: ...STALLATION 10 SAFETY 10 ESD PRECAUTIONS 11 GENERAL 11 MOUNTING THE CABINET 11 MAINS CONNECTIONS 12 CONNECTING THE BATTERIES 13 EARTH FAULT MONITORING 13 SETUP PROGRAMMING 14 LEVEL 3 ENGINEERING OPTIONS 14 ZONE INTERFACE FUNCTION 21 OPERATING 22 PANEL CONTROLS INDICATIONS 24 DISABLE MODE 24 TEST MODE 25 FAULT DIAGNOSIS 26 FUNCTIONALITY DURING A SYSTEM FAULT 27 USER INSTRUCTIONS 27 SERVICE MAINTENAN...

Страница 4: ...nockouts located at the top and rear of the cabinet An eight button keypad is used to control the system and allow access to the function options The three main buttons RESOUND red SILENCE blue and RESET green being much larger and colour coded to assist the end users Two or four fire zone circuits are provided plus two monitored sounder circuits Fire Fault VFCO relays Fire Fault switched negative...

Страница 5: ...Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESENMAR 01 Issue 6 0 3 ABOUT THIS PANEL CABINET Fire Detection System 57mm 80mm 260mm 308mm 250mm 300mm ...

Страница 6: ... THIS PANEL CIRCUIT BOARDS Esento Marine 2 4 zone panels comprise of two circuit boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 BATTERY 1 2 3 ON 1 2 3 4 ENTER RESOUND SILENCE RESET TPCA01 E2MAR E4MAR 2 or 4 zone Master PCB TPCA02 LED Display Controls PCB ...

Страница 7: ...tput fused 500mA 28v input for power supply Temperature compensation voltage control link Commmon fire VFCO relay unfused Max 3A 30vdc Commmon fault VFCO relay maintained fail safe unfused Max 3A 30vdc Common fire O P Common fault O P Alert pulses sounders Precint class change activates sounders Switched ve inputs Switched ve outputs Max load 40mA To 0 volts Relay Coil Conventional monitored sound...

Страница 8: ... Max current 3 amps Max input current 3 amps Input voltage 22vdc to 32vdc 28v 0v power output 28vdc supply output for fire alarm accessory relays etc Max continuous use 400mA Fused 500mA Fuse 500mA resettable fuse Common fire relay Fire relay contact Clean C O Max 3A 30vdc Unfused Common fault relay Maintained fault relay contact Clean C O Max 3A 30vdc Unfused Outputs FR FLT Switched ve voltage ou...

Страница 9: ...drawn by panel example 4 Zone I min 85mA 2 Zone I min 75mA Maximum ripple 1 0 V p p Supply and charger fault monitored Min max battery size and type 2 x 3 2Ahr 12volt VRLA Use Yuasa NP range batteries Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval Battery charging voltage 27 3 vdc nominal at 20 deg C Temperature compensated Battery charging output...

Страница 10: ...Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 8 DESIGN CONSIDERATIONS TYPICAL DETECTION CIRCUIT SCHEMATIC ...

Страница 11: ...pproved Document UI ESENMAR 01 Issue 6 0 9 DESIGN CONSIDERATIONS TYPICAL SOUNDER CIRCUIT SCHEMATIC 4K7 OHM END OF LINE RESISTOR SNDR1 MOTORISED BELL POLARISED MOTORISED BELL POLARISED ELECTRONIC SOUNDER POLARISED ELECTRONIC SOUNDER POLARISED VE VE VE VE VE VE VE VE ...

Страница 12: ...o take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned with its use This equipment is designed to be operated from 230V AC 50 60 Hz mains supplies and is of Class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation Failure to ensure that all cond...

Страница 13: ...used in the system must be suppressed to avoid damage to the control equipment This panel is only suitable for mounting in dry control rooms or dry accomodation spaces The site chosen for the location of the panel should be clean dry and not subject to shock or vibration Damp salt air or environments where water ingress or extremes of temperature may affect the panel must be avoided The temperatur...

Страница 14: ...upply should be brought into the panel via one of the knockouts provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable ring crimp Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while le...

Страница 15: ...ltage will appear on the output leads or terminals due to intelligent battery controls b Check the power supply voltage at the 28v 0v supply output terminals With the batteries disconnected the voltage should be 27 6vdc 0 2v between 11o C 40o C c To test the batteries turn off the mains and see if the system will run on the batteries Check the battery voltage should be 26 8v for a good battery or ...

Страница 16: ...l bleep to acknowledge the reset RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps To access Level 3 options first set switch 3 on the 3 way DIL switch located on the main PCB to the ON position Then activate the controls by entering the four digit code see Activate Controls in the OPE...

Страница 17: ...lse to indicate setting zone 1 to muster alarm Use button 1 to move the pulsing fire LED to the required zone and then use button 2 to change the setting indicated by the amber fault LED ON or OFF Any or all zones may be set for muster alarm ON muster alarm zone OFF standard Set RESOUND Button Operation For Muster Alarm LED 2 With the zone 2 fire LED lit press the ENTER button Fire LED 2 will now ...

Страница 18: ... 4 however this can be changed It is also possible to disable the use of a code entry to enable controls forcing the use of the key switch only With the zone 1 fire LED lit press the ENTER button Zone 1 fire LED will pulse to indicate edit mode and the amber fault LEDs will start to rapidly pulse in sequence to show the currently set code Enter the new code slowly and deliberately one number at a ...

Страница 19: ... Battery Monitoring EN54 Disable Battery Hi Z Monitoring EN54 The battery monitoring may be disabled for applications where this is appropriate such as non fire alarm use or where no battery backup is required Note There is no remote PSU fault input available on the panel This is also known as UPS Mode where the panel is supplied from a local 24v supply rather than mains and intenal batteries With...

Страница 20: ...ENTER button again will toggle the status indicated by a rapid or slow pulsing LED see below Then use Button 1 to move to the next zone If the zone has been set to not resound alarms the LED will be off If kept as default new fire condition will resound alarms then the LED will be on steady Rapid Pulse Zone is under selection and is set to have alarms resound default Slow Pulse Zone is under selec...

Страница 21: ...intrinsically safe barrier to be used in the circuit Detector removal monitoring EN54 The detector removal monitoring can be turned off For use with older non compliant detectors Enter the above code and press the ENTER button The zone 1 fire LED will light This indicates setting the above attributes for zone 1 The amber fault disabled test LEDs will show the current settings for that zone Use but...

Страница 22: ... table below The setting of the attribute is indicated by the amber fault LED ON or OFF Use button 2 to switch the attribute ON or OFF indicated by the amber fault LED Then use button 1 to move to the next attribute if required Press the ENTER button to return back to the zone selection indicated by a steady zone fire LED RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test ...

Страница 23: ...ton The Aux Output Status LED will pulse slowly Zone Fault LEDs will show their current status see below with Zone 1 pulsing to indicate it is under selection Use Button 1 Disable Mode to move to the zone for programming indicated by a pulsing LED and press the ENTER button to change the status Pressing the ENTER button again will toggle the status indicated by a rapid or slow pulsing LED see belo...

Страница 24: ...output Subsequent presses will toggle between them With the required fire LED lit press the ENTER button and Zone 1 fire LED will pulse Press button 2 Test Mode to alter the status of the output represented by the Zone 1 Fault LED either off or on Off Output cancels on RESET factory default On Output cancels on SILENCE ALARMS When the output status has been set press the ENTER button to return to ...

Страница 25: ...N 1 2 3 ON 1 2 3 4 5 6 7 ZONE2 ZONE3 ZONE4 C NC NO NO C NC FIRE FAULT optional PANEL 1 PANEL 2 470Ω 3K3Ω Example connection 4 3 4 4 Conventional Sounder Circuit Functional Options This option is used to programme each of the conventional sounder circuits on the main circuit board with custom reponses as below Enter the above code and press ENTER Then use button 1 to select the sounder circuit to b...

Страница 26: ...trols is enabled by default but can be disabled in the engineering functions To activate the controls using the key switch turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED will extinguish If the key switch is in...

Страница 27: ...n is operational without the need to activate controls Also has the numeric value 4 for code entry ENTER This button is used to confirm code entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 4 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 4 Indicates zone circuit is disabled or in test mode Indicates a fault in the zon...

Страница 28: ...election back to Zone 1 again When the desired circuit or output to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enabled Then use Disable Mode button again to move to the next circuit Any or all circuits can be disabled simultaneously Wh...

Страница 29: ...k to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next zone Any or all zones can be in test mode simultaneously When at the sounder status position use...

Страница 30: ... are not active The following table shows details of the indications in fault diagnosis mode RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps LED Indicator State before pressing ENTER LED Pulsing after pressing ENTER LED Steady after pressing ENTER LED Off after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circu...

Страница 31: ...sed the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer 5 When fully satisfied that there is no fire return to the control panel and press the green RESET button fig 3 The panel display should return to normal and only the green SUPPLY HEALTHY LED should be lit on the control panel A system fault is indicated when...

Страница 32: ...s no longer compliant with this part of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the premises management to supervise all matters pertaining to the fire detection and fire alarm system The role of this person is to ensure that the system is tested and maintained in accordance with the rec...

Страница 33: ...would normally be a qualified electrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis The maximum period between inspections must not exceed six months Recommendations of BS5839 1 for periodic service visits include Every device on the system should be...

Страница 34: ...F ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 32 ...

Страница 35: ...F ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 33 ...

Страница 36: ...F ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 34 ...

Страница 37: ...F ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 35 ...

Страница 38: ...F ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 36 ...

Страница 39: ...F ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 37 ...

Страница 40: ...MS FAULTS ENGINEERS VISITS Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 38 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Страница 41: ...MS FAULTS ENGINEERS VISITS Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 39 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Страница 42: ...MS FAULTS ENGINEERS VISITS Esento Marine 2 4 Installation Commissioning Operating Manual Approved Document UI ESEN4MAR 01 Issue 6 0 40 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Страница 43: ... and press the blue SILENCE ALARMS button fig 1 To sound the alarms again press the red RESOUND button fig 2 4 In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer 5 When fully satisfied that there is no fire return to the control panel and press the...