AlarmSense Installation, Commissioning & Operating Manual

Approved Document UI-ALS-01 Issue 2.0

6

ABOUT THIS PANEL

General Speci

fi

 cation

 Enclosure

Steel IP30. Epoxy powder coated Interpon Radon, silver grey

Temperature range

-5 deg C to +40 deg C max RH 95%

Number of AlarmSense circuits

2 or 4

Device compatibility

Apollo: AlarmSense only

TECHNICAL SPECIFICATION

Electrical Speci

fi

 cation Inputs & Outputs - TPCA06-A2/A4

Cabling

Fire resistant screened cable, minimum 
size 1mm

2

. Max cable length 1Km (20 

Ohm). FireBurn, FP200 or equivalent 
(max capacitance 1uF, max inductance 1 
millihenry).

Suitable cable glands must be used.

Terminal capacity

0.5mm

2

 to 2.5mm

2

 solid or stranded wire.

PSU @ output

Power supply voltage control line.

For temperature compensation control.

PSU Input + -

28vdc supply input. Diode protected for 
reversal and independent short circuit. 
Max current 3 amps.

Max input current 3 amps. Input voltage 
22vdc to 32vdc.

28v+, 0v- power output

28vdc supply output for 

fi

 re alarm 

accessory relays etc. Max continuous 
use = 400mA.

Fused @ 500mA. Fuse = 500mA 
resettable fuse.

Common 

fi

 re relay

Fire relay contact. Clean C/O. 
Max 3A @ 30vdc 

Unfused

Common fault relay

Maintained fault relay contact. Clean 
C/O. Max 3A @ 30vdc

Unfused

Outputs; FR, FLT

Switched -ve voltage outputs for relay 
control. 

Overload voltage protected to 52vdc. 
Current limited 680R. Max load = 40mA

Inputs; CC, PUL

Switched -ve inputs, connect to 0v to 
trigger. Max input voltage = 28vdc. Non 
latching, max resistance 100R.

Protected via 10K Ohm impedance, 3v6 
zener diode.

SNDR 1 - 2

28vdc polarity reversal monitored 
sounder outputs to 

fi

 re alarm devices. 

3K3 Ohm 5% 0.25W EOL resistor.

Monitoring current limit 28mA, fused @ 
500mA. Typical max load 22 devices @ 
18mA each per circuit. Ensure 0.9A is not 
exceeded.

Zone 1 - 4

AlarmSense 

fi

 re alarm zone circuits.

3K3 Ohm 5% 0.25W EOL resistor. 

Monitoring current limit 50mA, fused 
@ 200mA. Typical max load 20 alarm 
devices @ 18mA each per circuit. Ensure 
0.2A is not exceeded.

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание AlarmSense

Страница 1: ...Installation Commissioning Operating Manual EN54 APPROVED 2 4 ZONE ALARMSENSE CONTROL PANEL Approved Document UI ALS 01 Issue 2 0 810a 05 www acornfiresecurity com www acornfiresecurity com ...

Страница 2: ...39 Part 1 It is the responsibility of the This fire alarm system requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order system user to ensure it is regularly serviced and maintained in good working order Disclaimer Disclaimer No responsibility can be accepted by the manufacturer or ...

Страница 3: ... MAINS CONNECTIONS 12 CONNECTING THE BATTERIES 13 SETUP PROGRAMMING 14 WHAT IS ALARMSENSE 14 LEVEL 3 ENGINEERING OPTIONS 15 ZONE INTERFACE FUNCTION 22 LIST OF ALARMSENSE DEVICES 23 OPERATING 24 PANEL CONTROLS INDICATIONS 24 DISABLE MODE 26 TEST MODE 27 FAULT DIAGNOSIS 28 FUNCTIONALITY DURING A SYSTEM FAULT 29 USER INSTRUCTIONS 29 SERVICE MAINTENANCE 30 THE NEED FOR MAINTENANCE 30 DUTIES OF THE RES...

Страница 4: ... enable the controls via a 4 digit code entry if preferred An eight button keypad is used to control the to enable the controls via a 4 digit code entry if preferred An eight button keypad is used to control the system and allow access to the function options The three main buttons RESOUND red SILENCE system and allow access to the function options The three main buttons RESOUND red SILENCE blue a...

Страница 5: ...tallation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 3 ABOUT THIS PANEL CABINET Haes Systems AlarmSense 57mm 80mm 260mm 308mm 250mm 300mm www acornfiresecurity com www acornfiresecurity com ...

Страница 6: ...RDS AlarmSense panels comprise of two circuit boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 BATTERY 1 2 3 ON 1 2 3 4 ENTER RESOUND SILENCE RESET TPCA06 A2 A4 2 or 4 zone Master PCB TPCA02 LED Display Controls PCB www acornfiresecurity com www acornfiresecurity com ...

Страница 7: ...power supply Temperature compensation voltage control link Commmon fire VFCO relay unfused Max 3A 30vdc Commmon fault VFCO relay maintained fail safe unfused Max 3A 30vdc Common fire O P Common fault O P Alert pulses sounders Precint class change activates sounders Switched ve inputs Switched ve outputs Max load 40mA To 0 volts Relay Coil Conventional monitored sounder circuits fused 500mA AlarmSe...

Страница 8: ...ltage 22vdc to 32vdc 28v 0v power output 28vdc supply output for fire alarm accessory relays etc Max continuous use 400mA Fused 500mA Fuse 500mA resettable fuse Common fire relay Fire relay contact Clean C O Max 3A 30vdc Unfused Common fault relay Maintained fault relay contact Clean C O Max 3A 30vdc Unfused Outputs FR FLT Switched ve voltage outputs for relay control Overload voltage protected to...

Страница 9: ...Zone I min 75mA Maximum ripple 120 mV p p Supply and charger fault monitored Min max battery size and type 2 x 3 2Ahr 12volt VRLA Use Yuasa NP range batteries Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval Battery charging voltage 27 3 vdc nominal at 20 deg C Temperature compensated Battery charging output current 1 5A PSU 630mA Current limited 10...

Страница 10: ...f 112m2 per device When mounted on a flat ceiling heat detection devices have an individual coverage of 5 3m radius However these radii must overlap to ensure there are no blind spots Therefore individual coverage can be represented by a square measuring 7 5m x 7 5m giving an actual coverage of 56 3m2 per device Call Points A person should not have to travel more than 45m along an escape route to ...

Страница 11: ...h that cable The screen or drain wire of circuits should be bonded to earth at recommended for use with that cable The screen or drain wire of circuits should be bonded to earth at one location only and should be continuous throughout the circuit Drain wires should be terminated in the one location only and should be continuous throughout the circuit Drain wires should be terminated in the cabinet...

Страница 12: ...ions of the Act you are therefore requested to take such steps as are necessary to According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned ensure that any appropriate information about this product is made available by you to anyone concerned wit...

Страница 13: ...nd must be segregated away from mains voltage Any junction boxes used should be clearly labelled FIRE ALARM Any ancillary devices e g door retaining magnets must be powered from a separate power source Any coils or solenoids used in the system must be suppressed to avoid damage to the control equipment The site chosen for the location of the panel should be clean dry and not subject to shock or vi...

Страница 14: ...t into the panel via one of the knockouts provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using the ring crimp provided Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth conn...

Страница 15: ...te check connections The battery charging voltage is factory calibrated to 27 3vdc 0 2v 20o C This should not normally require adjustment Where battery problems are experienced the following information should be considered a If a battery is disconnected from the charger no voltage will appear on the output leads or terminals due to intelligent battery controls b Check the power supply voltage at ...

Страница 16: ...pecial programming options incorporated for use with AlarmSense devices Setting as to whether non priority mode is available per zone Programmable time delay for non priority alarms 30 60 or 120 seconds Panel display response during non priority alarms either no indication or zone LED with buzzer Non Priority Functionality When a sounder base has been set as non priority If smoke is detected the l...

Страница 17: ...on again and hold for 3 seconds Any disablements or test mode settings will now clear and all engineering option parameters will revert back to factory settings The panel will bleep to acknowledge the reset RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps To access Level 3 options fir...

Страница 18: ...an be changed It is also possible to disable the use of a code entry to enable controls forcing the use of the key switch only Enter the above code and press the ENTER button The Zone Fault Disabled Test LEDs will start to rapidly pulse in sequence to show the currently set code The sequence will be repeated twice after which time the panel will automatically drop out of the set keypad entry mode ...

Страница 19: ...oggle the status indicated by a rapid or slow pulsing LED see below Then use Button 1 to move to the next zone If the zone has been set to not resound alarms the LED will be off If kept as default new fire condition will resound alarms then the LED will be on steady Rapid Pulse Zone is under selection and is set to have alarms resound default Slow Pulse Zone is under selection and has been set to ...

Страница 20: ...ton 2 to change the amber LED to ON or OFF Press and hold button 1 to exit option Option 2 set alarm confirmation time WIth fire zone 2 LED lit press the ENTER button The delay time is represented by the amber fault LED on zone 1 2 3 Zone 1 fault LED ON 30 seconds Zone 2 fault LED ON 60 seconds Zone 3 fault LED ON 120 seconds default To change the delay time use button 1 to move to the zone amber ...

Страница 21: ...s a fire input signal This setting allows the panel to clear automatically when a fire signal is removed This is useful for interfacing purposes Short circuit as alarm EN54 For Older non EN54 or BS5839 compliant systems This allows a short circuit to activate a fire rather than a fault condition Enter the above code and press the ENTER button The zone 1 fire LED will light This indicates setting t...

Страница 22: ...abled test LED ON or OFF Use button 2 to switch the attribute ON or OFF indicated by the amber fault disabled test LED Then use button 1 to move to the next attribute if required Press the ENTER button to return back to the zone selection indicated by a steady zone fire LED RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable...

Страница 23: ...etween them With the required fire LED lit press the ENTER button and Zone 1 fire LED will pulse Press button 2 Test Mode to alter the status of the output represented by the Zone 1 Fault Disabled Test LED either off or on Off Output cancels on RESET factory default On Output cancels on SILENCE ALARMS When the output status has been set press the ENTER button to return to the output selection mode...

Страница 24: ...nel will Not operate sounders connected to the interface zone ZONE INTERFACE FUNCTION 1 2 3 ON P ZONE2 ZONE3 ZONE4 C NC NO NO C NC FIRE FAULT optional PANEL 1 PANEL 2 470Ω 3K3Ω Example connection 4 3 4 4 Conventional Sounder Circuit Functional Options This option is used to programme each of the conventional sounder circuits on the main circuit board with custom reponses as below Enter the above c...

Страница 25: ...5000 392 AlarmSense integrating optical detector and sounder base 55000 393 AlarmSense A1R heat detector and sounder base 55000 196 AlarmSense CS heat detector and sounder base 55000 197 AlarmSense optical smoke detector and sndr beacon base 55000 394 AlarmSense integrating optical detector sounder beacon 55000 395 AlarmSense A1R heat detector and sounder beacon base 55000 198 AlarmSense CS heat d...

Страница 26: ... can be disabled in the engineering functions To activate the controls using the key switch turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED will extinguish If the key switch is in the On position the keypad wil...

Страница 27: ... is operational without the need to activate controls Also has the numeric value 4 for code entry ENTER This button is used to confirm code entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 4 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 4 Indicates zone circuit is disabled or in test mode Indicates a fault in the zone...

Страница 28: ...one 1 again When the desired circuit or output to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enabled Then use Disable Mode button again to move to the next circuit Any or all circuits can be disabled simultaneously When all disablement...

Страница 29: ... When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next zone Any or all zones can be in test mode simultaneously When at the sounder status position use the ENTER button...

Страница 30: ...ble shows details of the indications in fault diagnosis mode RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps LED Indicator State before pressing ENTER LED Pulsing after pressing ENTER LED Steady after pressing ENTER LED Off after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK Main PCB SNDR 1 Zone 2 Fir...

Страница 31: ... alarm look for the device that has caused the alarm A detector will have a In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer 5 5 When fully sa...

Страница 32: ...part of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the premises management to supervise all matters pertaining to the fire detection and fire alarm system The role of this person is to ensure that the system is tested and maintained in accordance with the recommendations of BS 5839 Part 1 t...

Страница 33: ...ectrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis The maximum period between inspections must not exceed six months Recommendations of BS5839 1 for periodic service visits include Every device on the system should be tested annually The testing of ...

Страница 34: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 32 www acornfiresecurity com www acornfiresecurity com ...

Страница 35: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 33 www acornfiresecurity com www acornfiresecurity com ...

Страница 36: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 34 www acornfiresecurity com www acornfiresecurity com ...

Страница 37: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 35 www acornfiresecurity com www acornfiresecurity com ...

Страница 38: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 36 www acornfiresecurity com www acornfiresecurity com ...

Страница 39: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 37 www acornfiresecurity com www acornfiresecurity com ...

Страница 40: ...VISITS AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 38 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecurity com www acornfiresecurity com ...

Страница 41: ...VISITS AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 39 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecurity com www acornfiresecurity com ...

Страница 42: ...VISITS AlarmSense Installation Commissioning Operating Manual Approved Document UI ALS 01 Issue 2 0 40 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecurity com www acornfiresecurity com ...

Страница 43: ...at has caused the alarm A detector will have a In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer 5 5 When fully satisfied that there is no fire...

Страница 44: ...www acornfiresecurity com www acornfiresecurity com ...

Отзывы: