AlarmSense Installation, Commissioning & Operating Manual
Approved Document UI-ALS-01 Issue 2.0
21
SETUP & PROGRAMMING
4
2
4
2
Common
fi
re outputs cancel on silence alarms
The Common Fire VFCO relay output and the Common Fire switched -ve output, when activated, normally
remain until the panel is RESET.
This option changes these outputs to reset on SILENCE ALARMS. This may be useful for panel interlink
purposes.
Both outputs can be programmed independently.
Enter the above code and press the ENTER button.
The red Zone 1
fi
re LED will illuminate, this LED represents the Common Fire VFCO relay output.
Pressing Button 1 (Disable Mode) will move to red Zone 2
fi
re LED which represents the Common Fire
switched -ve output. Subsequent presses will toggle between them.
With the required
fi
re LED lit press the ENTER button and Zone 1,
fi
re LED will pulse.
Press button 2 (Test Mode) to alter the status of the output, represented by the Zone 1, Fault/Disabled/
Test LED either off or on.
Off = Output cancels on RESET (factory default)
On = Output cancels on SILENCE ALARMS
.
When the output status has been set, press the ENTER button to return to the output selection mode.
PSU
@
+
+
-
-
+
-
+
-
+
-
+
-
+
-
+
-
28V 0V
C
NC NO
C
NC NO
FIRE
FAULT
FR
FLT
CC
PUL
-OP -OP -IP -IP
SNDR1
SNDR2
ZONE1
ZONE2
ZONE3
ZONE4
C
ommmon
fir
e
VFC
O
re
l
ay
C
ommon
fir
e
O/P
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When
fi
nished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10
seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.