Operating Mode

The DMA2 is a strain gauge amplifier processes sensor signals in the analog mode. The parameter values, 

however, are digitally adjusted. LEDs indicate the operating status. The digital display shows the parameter 

value respectively the output signal.

Adjustment Modes

Zero adjust calibration

  - either automatically by key operation (details: see page 6)
  - or manual: moving the zero point by the amount of the web weight on  

    the measuring/idler roll
  The second possibility is useful if e.g. the web tension control system is preloaded with the defined web  

  weight either while in operation or at standstill. Another application can be e.g. a silo which cannot be  

  completely emptied and has a certain amount of weight remaining.

Amplification parameter defined by a value (gain)

  In this case the gain is calculated and correspondingly adjusted
  

Example

   

Sensor data:  

nominal rating 1,5 m V/V

   

 

bridge supply voltage: 10 V

  

 

(the output signal is therefore 15 mV = 0.015 V at nominal force)

   

Amplifier output:  10 V at nominal web tension

   

 

0 V at zero web tension

 
If the sensor is operating below its nominal force then the amplification must be increased.
  

Example

  

The maximum sensor load is only 75% of nominal force. 

 

 

The output signal is therefore only:  

  

this leads to:

Amplification adjustment with calibration weights

  In this operating modes the web tension measurement equipment is loaded with calibration weights  
  and the amplification is adjusted accordingly. This is the more realistic but more cumbersome method.

page 2

HAEHNE

  Elektronische Messgeräte GmbH · Heinrich-Hertz-Str. 29 · D-40699 Erkrath Germany · Telefon 0211/9 25 91-0 · Fax 0211/9 25 91-20

http://www.haehne.de 

Email: [email protected]

HAEHNE

15 mV •  75 %       =  11,25 mV
  

100 %

Gain  = 

10V       =  888,88  ≈ 888,9  

  

0,01125 V

Gain  = 

10V       =  666,66  ≈ 666,7  

  

0,015 V

The selected sequence of the adjustment steps is based on experience in practice situations. 

Other sequences of adjustment steps are certainly possible.

08.08 DE1DM2EA.indd 

Содержание DMA2

Страница 1: ...in 2 Amplification adjustment with calibration weights 2 Connection Wiring 3 Operation Preparation 4 Adjustment mode 4 Pre Adjustments Operationg Modes Display intensity 4 Filter type of the current output 4 Output signal range 5 Display value 5 Adjustement Of The Parameters Automatic zero point adjustment 6 Manual zero point adjustment 6 Entering amplification as gain value 6 Amplification adjust...

Страница 2: ...inal rating 1 5 m V V bridge supply voltage 10 V the output signal is therefore 15 mV 0 015 V at nominal force Amplifier output 10 V at nominal web tension 0 V at zero web tension If the sensor is operating below its nominal force then the amplification must be increased Example The maximum sensor load is only 75 of nominal force The output signal is therefore only this leads to Amplification adju...

Страница 3: ...y from the shield with PE Additional recommendation Connect the 0 V of the 24 V circuitry at a defined place prefably in close proximity of the PE If this reference point is to be operated in the floating point mode then the voltage between 0 V and PE should not exceed 50 Vpp The four terminal blocks with five terminals each can be separatly plugged in simplifying trouble shooting in case of fault...

Страница 4: ...re and the LED lights up until the procedure is completed The amplifier switches now automatically into the operating mode Leaving the adjustment mode without storage When exceeding the waiting time of 20 seconds the amplifier switches without changes automatically into the operating mode An alternative is pressing the menu key beyond the 8 menu step Display intensity 7 Menu step select the menu s...

Страница 5: ...ds to 10 V output voltage increasing The various decimal ranges are stepped through sequentially The step velocity increases with the key holding time This adjustment deletes stored peak values Output signal range 8 Menu step select the menu point output signal range in the adjustment mode select operating mode store adjustment Operating Mode Signal value Voltage output Current output Option C Opt...

Страница 6: ...sing adjustment range 10 0 100 Entering amplification as gain value 4 Menu step calculate amplification siehe section Adjustment Modes on page 2 if no sensor is connected then terminals 18 19 or 13 14 have to be connected with each other Select the menu point Gain in the adjustment mode select the desired amplification store the adjustment increasing decreasing adjustment range 400 2800 page 6 See...

Страница 7: ...nd is displayed in menu step 4 calculated amplification as gain value null The calibration weight is too small Model the web geometry with a cable or rope and apply calibration weight The weight should approxi mate the actual web tension in the operating mode The DMA2 offers the facility to increase the weight with a percentage calculation As an example 70 of the required 100 kg are applied to the...

Страница 8: ...the SET key max value min value Fault display during operation Exceeding the maximum output signal voltage of approximately 13 3 V e g resulting from a broken sensor cable HAEHNE Elektronische Messgeräte GmbH Heinrich Hertz Str 29 D 40699 Erkrath Germany Telefon 0211 9 2591 0 Fax 0211 9 2591 20 http www haehne de Email info haehne de HAEHNE page 8 08 08 DE1DM2EA indd ...

Отзывы: