GB
18
13. Cleaning and maintenance work (see Appliance sheet 3+4.)
14. Faults, causes, correction
You can correct simple operating faults yourself with the following guide. For further information please consult
your specialist dealer.
WARNING
If a fault occurs, you will be shown this on the display.
In the event of a fault, do not pull the mains plug out straight away, so that the internal safety functions
can continue to operate fully. Only in this way can the flue gases present be extracted via the chimney
using the fan. Only pull out the mains plug before starting work on the cold appliance.
14.1. Fault – error code Fxxx
Code
Cause:
Correction:
F001
A. STL triggered due to
overheating
B. Fuse (F1) in the central unit is
defective
C. Ignition short circuit
A. If STB has triggered - contact
service department
B. Fuse F1(3.15 A) defective -
contact service department
C. Ignition defective - contact
service department
F002
A. Burner dirty
B. Pellet tank empty
C. Ignition defective
D. Burner not lying flush
E. Flame temperature sensor
defective
F. Downpipe / screw conveyor
blocked
G. Screw motor defective
A. Clean burner
B. Clean burner - fill pellet tank
C. Ignition defective - contact
service department
D. Clean burner - position burner
correctly
E. Flame temperature sensor
defective - contact service
department
F. Clean the intake on the screw
conveyor housing with a vacuum
cleaner - clean burner
G. Screw motor defective -
contact service department
F003
A. Heat exchanger / smoke flues
dirty
B. Heating curve set too low
C. Room temperature sensor is
lying on the floor or wall
A. Cleaning the smoke flues -
clean burner
B. Clean burner - Adjust heating
curve as described
C. Clean burner - suspend room
temperature sensor freely
F005
A. Burner dirty
B. Pellet tank empty
C. Downpipe / screw conveyor
blocked
D. Room too airtight – required
combustion air cannot flow into
the room
E. Flue gas temperature sensor
defective
F. Screw motor defective
A. Clean burner
B. Clean burner - fill pellet tank
C. Clean the intake on the screw
conveyor housing with a vacuum
cleaner. – Clean burner
D. Clean burner - Ensure
adequate combustion air
E. Flue gas temperature sensor
defective - contact service
department