GB
16
The whole "start zone" can go through up to 20 zones. It finishes after reaching a precisely defined
temperature at the "flame temperature sensor" and the control system puts the stove into "Heating mode".
The duration of the "start zone" can therefore vary.
If, during the start zone, no flame generation can be achieved or the required temperature at the "flame
temperature sensor" cannot be reached, a shut down process is initiated.
10.2. Heating mode
After the positive conclusion of the
"start zone"
, the stove automatically switches to
"Heating mode"
.
In "Heating mode", the heat output of the stove is adjusted in modular fashion to the room temperature or to
the difference between the Actual and Target room temperatures.
If the difference between the Actual and Target room temperatures is big, then the stove heats with a bigger
heat output.
The nearer the Actual and Target room temperatures get to each other, the more the stove's heat output is
reduced.
10.3. Burner test (burner cleaning)
During the "Heating mode" operating status, an automatic burner cleaning process is carried out at regular
time intervals (E.G. 30 minutes).
This process takes approx. 2 minutes.
10.4. Cooling down
If the set Target room temperature is reached or the "ON/OFF" button is pressed, then the operating status
switches to "cooling down". The cooling down phase is restricted by timing control (duration about 15
minutes). After the end of the "Cooling down" operating status, the appliance switches to "standby" operating
status or "OFF".
10.5. ECO-Mode
ECO-Mode means continuous operation at a low output, if the "Actual room temperature" is higher than the
set "Target room temperature" i.E. the stove does not switch off but continues to run on a "smaller flame".
If the set "Target room temperature" is exceeded by more than 2 °C, in ECO-Mode despite a small flame,
• ECO-Mode is automatically switched off and the stove switches to the "cooling down" operating status.
• ECO-Mode function is automatically deactivated.
If an "Actual room temperature" of 30 ° C is exceeded in ECO-Mode, ECO-Mode function is automatically
deactivated.
10.6. Standby
The stove is in waiting condition. Before it can be switched over from the operating setting "standby" to the
operating setting "Start zones 1 – 20", two conditions for the start are to be fulfilled:
• The "Actual room temperature" must drop under the "Target room temperature" by 1 °C at least
• The temperature of the combustion products measured by temperature sensor must be lower than 70 °C