It is NOT recommended to use the device for long time under condensation conditions. It could
be the cause of water steam condensation inside the sensor’s cover into water phase. This liquid phase
stays inside sensor’s cover and can’t escape from the cover easily. It can dramatically increase
response time to relative humidity change. If water condensation occurs for longer time it can cause
sensor damage. Similar effect can occur under water aerosol conditions.
External temperature probe connectable to
AR006683 must be type of “two wires
with shielding”. The probe cable length and
size of conductor affects measurement
accuracy. If connected probe is equipped
with metal stem, we recommend using
probes with metal stem not connected to
cable shielding. Or else it is necessary to
arrange metal stem is not connected to
any other circuitry.
The cables for binary inputs and external
sensor for regulator AR006683 must be
placed as far as possible from potential
interference sources. The cables should not be
led in parallel along power cabling. Safety
distance is up to 0.5 m, otherwise
undesirable
induction
of interference
signals can appear. Maximum cable length
is 10 m. Connect cable shielding to proper
terminal and do not connect it to any other
circuitry and do not ground it.