Issue 07/2011
Page 22
Bu
ilt
-in g
en
er
at
or
s w
ith s
w
itch c
ab
in
et f
or p
er
m
an
en
tly i
ns
ta
lle
d p
ow
er g
en
er
at
io
n s
ys
te
m
s ≥ 1
2 k
VA i
n fi
re e
ng
in
es
Description of power generation system
Switch cabinet
Legend for figures 3, 4 and 5:
1
Frequency display
2
Ammeter for each phase conductor
(nominal current marked on scale)
3
Voltmeter 0 V to 500 V.
Nominal voltage 230 V for measurement L1-N, L2-N or L3-N.
Nominal voltage 400 V for measurement L1-L2, L1-L3 or L2-L3.
4
Change-over switch, voltmeter
5
Operating hours counter for generator
6
Protective earth test device with test socket
7
Insulation monitor with optical and acoustic indication,
acknowledgment and check button
8
Four-pole 16 A circuit breaker (optional 32 A built-in power socket)
with thermal and magnetic tripping for CEE power sockets (No. 12)
9
Four-pole main circuit breaker with thermal and magnetic tripping.
Also serves as main switch for manual disconnect
10
Two-pole 16 A line circuit breaker with thermal and magnetic
tripping for power sockets (No. 11.1 and 11.2)
11.1
Two-pole power sockets with protective earth, 16 A/250 V.
Emergency power socket. Not protected by insulation monitor.
Only 1 consumer may be connected!
11.2 Two-pole power socket with protective earth, 16 A/250 V
12
CEE socket (AC), 5-pole with protective earth, 16 A/400 V, 3 L + N + PE
(optional 1 32 A power socket)
13
Switch cabinet lighting, supplied by on-board power supply
14
Switch for switch cabinet lighting