Page 11
Issue 07/2011
Safety instructions
Danger
Danger to life through electric shock
y
Working on the generator or switch cabinet, visual inspections
for maintenance purposes or cleaning work on the power
generation system during operation can lead to potentially
fatal injuries through electric shock.
►
Switch off the drive unit before performing any inspection
or maintenance work on the generator or switch cabinet.
Prevent the drive unit from being switched back on by
accident (e.g. remove the ignition key and keep somewhere
safe).
Danger
Danger to life through electric shock
y
A grounding of the neutral conductor of the generator
(N, neutral conductor) invalidates the “electrical separation”
protective measure.
►
Never ground the neutral conductor of the generator.
Danger
Danger to life through electric shock
y
Insulation monitors can mutually influence each other.
►
Do not connect any other insulation monitors downstream
of the power generation system.