CONTROL BOARD SETTINGS

THESE SETTINGS SHOULD BE ADJUSTED ONLY BY AN EXPERIENCED INSTALLER OR TECHNICIAN!

RST/LEARN: 

1)

 

Use to set transmitter code in control board memory.

         2) Press this button to clear the diagnostic and error LEDs.

DIP switches 

(To change these settings, you must turn power OFF; move

the switch; then turn power back ON.)
SWNG/SLD (swing or slide gate operation): SWNG = swing gate  SLD = slide
gate  [factory default is SWNG].
MAST/SLV (master or slave unit): The DIP switch must be set to MAST
(OFF) for single gate applications.  For dual gate applications set one control
board to MAST and the other to SLV [factory default is MAST].  See Installing
a Dual System on pages 22-23.
GATE R/L (gate closes to the right or left): The direction a gate closes is
determined by standing inside the property and facing toward the gate.  Set the
DIP switch to R (OFF) for a gate that closes to the right.  Set the DIP switch to
(ON) for a gate that closes to the left.
SEQUENCE 1: This DIP switch is used for sequencing swing gates [factory default is OFF]. For single gate
applications this switch MUST be set to OFF.
SEQUENCE 2
: Same as SEQUENCE 1 above.
TMR. OFF/ON (auto-close timer OFF or ON; close timer is set to 1 second at the factory): When this DIP switch is
set to ON, the CLOSE TIMER potentiometer must be adjusted [factory default is OFF].

Potentiometers 

(All potentiometers are set to MIN  at the factory.  The size and type of gate

installation must be accommodated by adjusting the potentiometers.  HOWEVER–potentiometer
settings should not be used to compensate for worn, damaged, or incorrect gate hardware.)

CLS. SENS. (closing sensitivity): Adjusts obstruction sensitivity of the gate in closing mode.  The
MIN setting is for minimum gate force.  The MAX setting is for maximum gate force (i.e., the

operator will require greater resistance before obstructing).
OPN. SENS. (opening sensitivity): Adjusts obstruction sensitivity of the  gate in opening mode (see

CLS. SENS. above).
INERTIA: Fine tunes the operator obstruction settings in the open and close modes.  This

potentiometer can be adjusted to allow the operator to push an obstruction a maximum of 2 seconds
above set obstruction levels before shutting down.

CLOSE TIMER: Controls the auto-close feature (factory
default is 1 s).  It is disabled and enabled with the TMR. OFF/

ON DIP switch (see DIP switches above).  The potentiometer
adjusts the amount of time the gate will remain open before
it closes.  The limits are 1 to 120 seconds.

Diagnostic LEDs 

(Press RST / LEARN to clear these LEDs)

PWR OK: Power (115 Vac) is being delivered to the unit.
This light will not be on when the operator is in “LEARN” mode and will
PULSE when the system is on battery backup..
TIMER ON: The auto-close timer has been enabled.
OBSTRUCT: An obstruction has been encountered.
MAX TIME: Indicates operator ran longer than
60 seconds without reaching a limit switch and the motor has shut OFF.

MIN

MAX

CLS. SENS.

MIN

MAX

OPN. SENS.

MIN

MAX

INERTIA

1

120

60

CLOSE TIMER

Potentiometers

PWR OK

TIMER ON

OBSTRUCT

MAX TIME

SENSOR ERR.

LIM SW ERR.

OPEN MTR.

INTERN.ERR.

Diagnostic LEDs

123456

ON

SWNG/SLD

MAST/SLV

GATE R/L

SEQUENC 1

SEQUENCE 2

TMR. OFF/ON

EDGE 6

EDGE 5

 ST / LEARN

DIP switches

Содержание /PRO SW-5100

Страница 1: ...lates gate operator safety as established and made effective March 1 2000 by Underwriters Laboratories Inc WARNING READ ALL INSTRUCTIONS COMPLETELY before attempting installationanduse failuretodosoma...

Страница 2: ...general public Restricted Access Vehicular Gate Operator Class IV A vehicular gate operator or system intended for use in a guarded industrial location or building such as an airport security area or...

Страница 3: ...ing Labels 7 Technical Specifications 8 Parts Identification 9 Installing the Gate Operator 11 Preparation of the Gate 11 Operator Installation Overview 11 Using the Mounting Template 12 Removing the...

Страница 4: ...nd allows the gate to be opened and closed manually Use the GTO FOOT PEDAL RELEASE Patented to Manually Operate the Gate Because automatic gate operators produce high levels of force all system design...

Страница 5: ...stem to become familiar with its safety features Understand how to disengage and re engage the operator foot pedal release see GTO Foot Pedal Release on page 1 5 This gate operator is intended for veh...

Страница 6: ...oot pedal release 2 Inform the consumer end user that servicing of the operator must only be done by an experienced technician 3 Attach the warning signs included to each side of the gate to alert pub...

Страница 7: ...of a vehicular swing gate system B A hard wired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanic...

Страница 8: ...see page 6 Make sure the knuckle cover warning decals two are affixed to the knuckle cover 9 It is your responsibility to make sure that the installer posted warning signs on both sides of your gate I...

Страница 9: ...provide the gate operator with an integral safety feature by stopping and reversing gate direction upon sensing an obstruction Warning signs alert people of automatic gate operation Safety covers pre...

Страница 10: ...to operate gate or play in gate area 3 This entrance is for vehicles only Pedestrians must use a separate entrance 4 Read the owner s manual and safety instructions 5 For gate operators using Type D e...

Страница 11: ...s Control Adjustable auto close timer 1 120 seconds Independent obstruction settings for opening and closing cycles Diagnostic and error condition LEDs Potentiometers and DIP switches for easy adjustm...

Страница 12: ...00 SW 6000 AC Powered Swing Gate Operators WARNING Installation Instructions for GTO PRO SW 5000 SW 6000 AC Powered Swing Gate Operators WARNING Nylon Cable Ties 8 Hardware Reducer Arm Gate Arm Stop B...

Страница 13: ...itch Drive Sprockets and Chain Reducer Arm Gate Arm Stop Bracket Spline Release Fork Gate Arm Adjusting Bracket Foot Pedal Release Operator Frame Housing Standoffs Control Box ON OFF Switch 115 Vac du...

Страница 14: ...view The diagram below is an example of a single swing gate installation with required safety features The operator must be installed on the inside of the gate You must install safety edges or photoel...

Страница 15: ...the pad according to the instructions on the template Before you attempt to mount the operator check the following The concrete pad is level Four 4 1 2 diameter mounting anchors are in their correct...

Страница 16: ...e lower and upper splines see illustrations on page 1 and 10 Housing Knuckle Cover 2 ft square area 15 center to center mounting holes 15 875 center to center mounting holes Center point of gate hinge...

Страница 17: ...bolt holes of the parts and join them with 1 1 2 bolt 2 Fit the ends of the reducer arm stop bracket and gate arm together see illustration Align the bolt holes of the parts and join them with 1 1 2 b...

Страница 18: ...ngertip roll the limit nuts along the travel shaft until the correct open and closed gate positions are determined If the operator is mounted to the LEFT of the gate see illustration below the left li...

Страница 19: ...FF ON EDGE 6 EDGE 5 EDGE 4 EDGE 3 EDGE 2 EDGE 1 COM COM DUAL GATE INTER FACE RX TX G R B GTO RCVR 1 2 amp slow blow fuse CLOSE OPEN FIRE DEPT SHAD LOOP SAFE LOOP ENTRY LOOP FREE EXIT CYCLE COMMON COMM...

Страница 20: ...EVER potentiometer settings should not be used to compensate for worn damaged or incorrect gate hardware CLS SENS closing sensitivity Adjusts obstruction sensitivity of the gate in closing mode The MI...

Страница 21: ...commodates accessory power up to 1 2 A This is a fused power supply 1 2 A 3AG fuse only CAUTION Accessories other than 24 Vdc or rated higher than 1 2 A require a separate power supply not provided AU...

Страница 22: ...for receiver to charge C Press transmitter button until PWR OK light comes on Inc Inc Inc FCC Regulation This device complies with FCC rules Part 15 Operation is subject to the following conditions 1...

Страница 23: ...e spline retainer Lift the upper spline and the gate arm assembly as a unit off the output shaft of the gear reducer NOTE check to make sure the knuckle cover and its bolts are still in place see page...

Страница 24: ...rides Siren Operating Signal 3315 Addison Ave E Twin Falls ID 83301 Phone 800 767 4283 Fax 208 734 0829 Miscellaneous Gate Hinges DAC Industries Inc 982 Maple Hill S E Grand Rapids MI 49546 Phone 800...

Страница 25: ...Safety Edges wired to unit it controls Adjustable Inertia and Adjustable Sensitivity each unit controls its own gate A dual gate operator system requires a 5 wire connection between two single units...

Страница 26: ...M TX G R B GTO RCVR TB3 TB2 DUAL GATE INTER FACE RX COM COM TX G R B GTO RCVR TB3 TB2 Dual Gate Interface Auxiliary Control Board SLV Master Control Board MAST Use 22 AWG minimum individually shielded...

Страница 27: ...e Cover Pivot Cover Warning Sign Master Operator Slave Operator Use Rigid Conduit for inbound AC Use Rigid Conduit for inbound AC Use PVC Conduit for Receiver Safety Edge Safety Edge Dual Gate Interfa...

Страница 28: ...ce DO NOT ADD OIL Check hinges on the gate and lubricate if needed Check for loose or corroded wires Clean and grease the upper and lower splines twice per year Make sure the warning signs see page 7...

Страница 29: ...ts the receiver may be damaged Call the GTO Service Department C DisconnecttheaccessoriesfromthecontrolboardandjumpertheCYCLE terminal Iftheunitoperates then reconnect each accessory and test each one...

Страница 30: ...used by lightning wind fire flood insects or other natural agent This warranty gives you specific legal rights and you may also have other rights which may vary from state to state This warranty is is...

Страница 31: ...fied in the IMPORTANT SAFETY INSTRUCTIONS ___ Safety instructions were reviewed with the customer ___ The IMPORTANT SAFETY INSTRUCTIONS manual was given to the customer ___ Customer was instructed abo...

Отзывы: