prepArAtion For coMMissioning
10
ADICOS GTL-3
430-2410-102 EN11
5 Preparation for commissioning
NOTICE!
The ADICOS GTL-3 tester works by means of controlled combustion, which can
cause fires and explosions if used improperly.
• Do not open the housing within hazardous areas
5.1 Inserting the embers filter
The GTL-3 glow filter prevents the escape of embers and hot ashes during operation. As
soon as the filter is polluted and clogged with fire deposits, it must be replaced before next
operation.
Tips and recommendations
A clogged glow filter blocks the proper emission of test gases and therefore
leads to incorrect test results.
Insert / replace embers filter
1
Press the gas funnel downwards; pull the em-
bers filter holder upwards
2
Remove and dispose of used embers filter
3
Place new embers filter over the opening
4
Clamp new embers filter with embers filter hold-
er