12V
Wiring Diagram with Slave Reader
12V Linear
Power supply
Door Exit Button
0V
Door
Contact
0V
Common the OV from the
Fire Alarm Panel and the OV
from the Door Control to
avoid any ground loop issues.
Fire Alarm
Panel
0V
When the fire alarm
is activated (0V removed
from IP4) the door will
be opened
12V
Sounder
6
Wiring Diagrams
Smart Slave
(See page 14 for
wiring diagram)
12V
0V
NO
COM
NC
12 - 24 VAC
12 - 24 VAC
Wiring for StikeLock only using 12 - 24VAC supply
Note: All OV shown in the
diagram are connected to
OV of the Door Control.
0V
0V
OP1
Data0/Data
IP3
Data1/Clock
IP4
Fire Alarm
IP2
Door
Contact
IP1
Door Exit
Button
OP2
Alarm/Sounder
12V DC
Only
0V
BreakGlass Unit
Max
Data
Cable
Length
-100m
Shielded
Cable
Note: Fire Alarm Override is
deactivated until the Door
Control joins a network.
16V
Varistor
16V
Varistor
12V
0V
NO
COM
NC
IP1
IP2
IP3
IP4
OP1
OP2
A
B
T
AMP
T
AMP
485 Network Connection A & B
Common the OV from the Door
Control and the COM on the
Controllers “Door Network”
when using the 485 interface.
Place a 120ohm Termination
Resistor across A & B at the
Controller and on the last Door
in the daisy chain.
12V
0V
NO
COM
NC
IP1
IP2
IP3
IP4
OP1
OP2
A
B
T
AMP
T
AMP
1
2
3
4
5
6
Arm Alarm Input
Arm Output (N/O)
IP3
OP1
7
Wiring Diagrams
12V
Wiring Diagram with Intruder Alarm Panel
12V Linear
Power supply
Door Exit Button
0V
Door
Contact
0V
Common the OV from the
Fire Alarm Panel and the OV
from the Door Control to
avoid any ground loop issues.
Fire Alarm
Panel
0V
When the fire alarm
is activated (0V removed
from IP4) the door will
be opened
12V
Sounder
12V
0V
NO
COM
NC
12 - 24 VAC
12 - 24 VAC
Wiring for StikeLock only using 12 - 24VAC supply
Note: All OV shown in the
diagram are connected to
OV of the Door Control.
0V
0V
IP4
Fire Alarm
IP2
Door
Contact
IP1
Door Exit
Button
OP2
Alarm/Sounder
12V DC
Only
0V
BreakGlass Unit
Note: Fire Alarm Override is
deactivated until the Door
Control joins a network.
16V
Varistor
16V
Varistor
12V
0V
NO
COM
NC
IP1
IP2
IP3
IP4
OP1
OP2
A
B
T
AMP
T
AMP
485 Network Connection A & B
Common the OV from the Door
Control and the COM on the
Controllers “Door Network”
when using the 485 interface.
Place a 120ohm Termination
Resistor across A & B at the
Controller and on the last Door
in the daisy chain.
12V
0V
NO
COM
NC
IP1
IP2
IP3
IP4
OP1
OP2
A
B
T
AMP
T
AMP
1
2
3
4
5
6